Synchronization via IEC60870-5-103
The IEC60870-5-103 communication can be the source for the coarse time
synchronization, while the fine tuning of the time synchronization needs a source with
higher accuracy. See the communication protocol manual for a detailed description of
the IEC60870-5-103 protocol.
17.2.9
Technical data
Table 498:
Time synchronization, time tagging
Function
Value
Time tagging resolution, events and sampled measurement values
1 ms
Time tagging error with synchronization once/min (minute pulse
synchronization), events and sampled measurement values
± 1.0 ms typically
Time tagging error with SNTP synchronization, sampled measurement
values
± 1.0 ms typically
17.3
Parameter setting group handling
17.3.1
Functionality
Use the four different groups of settings to optimize the IED operation for different
power system conditions. Creating and switching between fine-tuned setting sets,
either from the local HMI or configurable binary inputs, results in a highly adaptable
IED that can be applied to a variety of power system scenarios.
17.3.2
Setting group handling SETGRPS
17.3.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Setting group handling
SETGRPS
-
-
17.3.2.2
Settings
Table 499:
SETGRPS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ActiveSetGrp
SettingGroup1
SettingGroup2
SettingGroup3
SettingGroup4
-
-
SettingGroup1
ActiveSettingGroup
MaxNoSetGrp
1 - 4
-
1
1
Max number of setting groups 1-4
1MRK 502 048-UEN A
Section 17
Basic IED functions
629
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...