SPVNZBAT activates the start and alarm outputs when the battery terminal voltage
exceeds the set upper limit or drops below the set lower limit. A time delay for the
overvoltage and undervoltage alarms can be set according to definite time
characteristics.
SPVNZBAT operates after a settable operate time and resets when the battery
undervoltage or overvoltage condition disappears after settable reset time.
14.14.4
Signals
Table 414:
SPVNZBAT Input signals
Name
Type
Default
Description
U_BATT
REAL
0.00
Battery terminal voltage that has to be supervised
BLOCK
BOOLEAN
0
Blocks all the output signals of the function
Table 415:
SPVNZBAT Output signals
Name
Type
Description
AL_ULOW
BOOLEAN
Alarm when voltage has been below low limit for a
set time
AL_UHI
BOOLEAN
Alarm when voltage has exceeded high limit for a
set time
ST_ULOW
BOOLEAN
Start signal when battery voltage drops below
lower limit
ST_UHI
BOOLEAN
Start signal when battery voltage exceeds upper
limit
14.14.5
Settings
Table 416:
SPVNZBAT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation mode Off / On
RtdBattVolt
20.00 - 250.00
V
1.00
110.00
Battery rated voltage
BattVoltLowLim
60 - 140
%Ubat
1
70
Lower limit for the battery terminal voltage
BattVoltHiLim
60 - 140
%Ubat
1
120
Upper limit for the battery terminal voltage
tDelay
0.000 - 60.000
s
0.001
0.200
Delay time for alarm
tReset
0.000 - 60.000
s
0.001
0.000
Time delay for reset of alarm
Section 14
1MRK 502 048-UEN A
Monitoring
552
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...