14.4.6.1
Disturbance information
Date and time of the disturbance, the indications, events, fault location and the trip
values are available on the local HMI. To acquire a complete disturbance report the
user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP or
MMS (over 61850) client. The PC can be connected to the IED front, rear or remotely
via the station bus (Ethernet ports).
14.4.6.2
Indications
Indications is a list of signals that were activated during the total recording time of the
disturbance (not time-tagged), see Indication section for detailed information.
14.4.6.3
Event recorder
The event recorder may contain a list of up to 150 time-tagged events, which have
occurred during the disturbance. The information is available via the local HMI or
PCM600, see Event recorder section for detailed information.
14.4.6.4
Event list
The event list may contain a list of totally 1000 time-tagged events. The list
information is continuously updated when selected binary signals change state. The
oldest data is overwritten. The logged signals may be presented via local HMI or
PCM600, see Event list section for detailed information.
14.4.6.5
Trip value recorder
The recorded trip values include phasors of selected analog signals before the fault and
during the fault, see Trip value recorder section for detailed information.
14.4.6.6
Disturbance recorder
Disturbance recorder records analog and binary signal data before, during and after
the fault, see Disturbance recorder section for detailed information.
14.4.6.7
Time tagging
The IED has a built-in real-time calendar and clock. This function is used for all time
tagging within the disturbance report
14.4.6.8
Recording times
Disturbance report DRPRDRE records information about a disturbance during a
settable time frame. The recording times are valid for the whole disturbance report.
Disturbance recorder, event recorder and indication function register disturbance data
and events during tRecording, the total recording time.
Section 14
1MRK 502 048-UEN A
Monitoring
530
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...