1
QC3ITL
QC3REL
en04000551.vsd
VPQB62
VPQB9
QB61_OP
QB62_OP
QB9_OP
VPQB9
VPVOLT
QB9_OP
VOLT_OFF
&
&
VPQB61
1
QC9ITL
QC9REL
IEC04000551 V1 EN
12.3.8.5
Signals
Table 251:
DB_BUS_A Input signals
Name
Type
Default
Description
QA1_OP
BOOLEAN
0
QA1 is in open position
QA1_CL
BOOLEAN
0
QA1 is in closed position
QB1_OP
BOOLEAN
0
QB1 is in open position
QB1_CL
BOOLEAN
0
QB1 is in closed position
QB61_OP
BOOLEAN
0
QB61 is in open position
QB61_CL
BOOLEAN
0
QB61 is in closed position
QC1_OP
BOOLEAN
0
QC1 is in open position
QC1_CL
BOOLEAN
0
QC1 is in closed position
QC2_OP
BOOLEAN
0
QC2 is in open position
QC2_CL
BOOLEAN
0
QC2 is in closed position
QC3_OP
BOOLEAN
0
QC3 is in open position
QC3_CL
BOOLEAN
0
QC3 is in closed position
QC11_OP
BOOLEAN
0
Earthing switch QC11 on busbar WA1 is in open
position
QC11_CL
BOOLEAN
0
Earthing switch QC11 on busbar WA1 is in closed
position
EXDU_ES
BOOLEAN
0
No transmission error from bay containing earthing
switch QC11
QB61_EX1
BOOLEAN
0
External condition for apparatus QB61
QB61_EX2
BOOLEAN
0
External condition for apparatus QB61
QB1_EX1
BOOLEAN
0
External condition for apparatus QB1
QB1_EX2
BOOLEAN
0
External condition for apparatus QB1
Table 252:
DB_BUS_B Input signals
Name
Type
Default
Description
QA2_OP
BOOLEAN
0
QA2 is in open position
QA2_CL
BOOLEAN
0
QA2 is in closed position
QB2_OP
BOOLEAN
0
QB2 is in open position
QB2_CL
BOOLEAN
0
QB2 is in closed position
Table continues on next page
1MRK 502 048-UEN A
Section 12
Control
391
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...