11.1.5
Settings
Table 200:
SDDRFUF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off / On
OpMode
Off
UNsINs
UZsIZs
UZsIZs OR UNsINs
UZsIZs AND
UNsINs
OptimZsNs
-
-
UZsIZs
Operating mode selection
3U0>
1 - 100
%UB
1
30
Operate level of residual overvoltage
element in % of UBase
3I0<
1 - 100
%IB
1
10
Operate level of residual undercurrent
element in % of IBase
3U2>
1 - 100
%UB
1
30
Operate level of neg seq overvoltage
element in % of UBase
3I2<
1 - 100
%IB
1
10
Operate level of neg seq undercurrent
element in % of IBase
OpDUDI
Off
On
-
-
Off
Operation of change based function
Off/On
DU>
1 - 100
%UB
1
60
Operate level of change in phase voltage
in % of UBase
DI<
1 - 100
%IB
1
15
Operate level of change in phase current
in % of IBase
UPh>
1 - 100
%UB
1
70
Operate level of phase voltage in % of
UBase
IPh>
1 - 100
%IB
1
10
Operate level of phase current in % of
IBase
SealIn
Off
On
-
-
On
Seal in functionality Off/On
USealln<
1 - 100
%UB
1
70
Operate level of seal-in phase voltage in
% of UBase
IDLD<
1 - 100
%IB
1
5
Operate level for open phase current
detection in % of IBase
UDLD<
1 - 100
%UB
1
60
Operate level for open phase voltage
detection in % of UBase
Table 201:
SDDRFUF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
1MRK 502 048-UEN A
Section 11
Secondary system supervision
309
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...