10.1.4
Signals
Table 184:
SAPTUF Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
Table 185:
SAPTUF Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
START
BOOLEAN
General start signal
RESTORE
BOOLEAN
Restore signal for load restoring purposes
BLKDMAGN
BOOLEAN
Measurement blocked due to low voltage
amplitude
10.1.5
Settings
Table 186:
SAPTUF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
StartFrequency
35.00 - 75.00
Hz
0.01
48.80
Frequency set value
tDelay
0.000 - 60.000
s
0.001
0.200
Operate time delay
tRestore
0.000 - 60.000
s
0.001
0.000
Restore time delay
RestoreFreq
45.00 - 65.00
Hz
0.01
49.90
Restore frequency if frequency is above
frequency value
10.1.6
Monitored data
Table 187:
SAPTUF Monitored data
Name
Type
Values (Range)
Unit
Description
FREQ
REAL
-
Hz
Measured frequency
10.1.7
Operation principle
The underfrequency protection (SAPTUF) function is used to detect low power
system frequency. If the frequency remains below the set value for a time period
greater than the set time delay the TRIP signal is issued. To avoid an unwanted trip due
to uncertain frequency measurement at low voltage magnitude, a voltage controlled
blocking of the function is available from the preprocessing function, that is, if the
Section 10
1MRK 502 048-UEN A
Frequency protection
296
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...