9.4.7.6
Logic diagram
IEC09000161_3_en.vsd
t
t
t
1
&
&
Ei
M=
(Ei / f)
(Ur / fr)
M = relative V/Hz as service value
V/Hz>>
M>V/Hz>>
V/Hz>
M>V/Hz>
tAlarm
tMin
kForIEEE
Calc ulation
of inte rnal
induced
voltage Ei
k
M
M
t>tAlarm
t>tMin
ALARM
AlarmL evel
1800 s
U3P
BLOCK
100 ms
TRIP
IEC09000161 V3 EN
Figure 141:
A simplified logic diagram of the Overexcitation protection
OEXPVPH
Simplification of the diagram is in the way the IEEE delays are calculated. The
cooling process is not shown. It is not shown that voltage and frequency are separately
checked against their respective limit values.
9.4.8
Technical data
Table 177:
OEXPVPH technical data
Function
Range or value
Accuracy
Operate value, start
(100–180)% of (
UBase/f
rated
)
± 0.5% of U
Operate value, alarm
(50–120)% of start level
± 0.5% of U
r
at U ≤ U
r
± 0.5% of U at U > U
r
Operate value, high level
(100–200)% of (
UBase/f
rated
)
± 0.5% of U
Curve type
IEEE
2
(0.18 )
:
(
1)
k
IEEE t
M
×
=
-
EQUATION1319 V1 EN
(Equation 93)
where M = (E/f)/(Ur/fr)
± 5% + 40 ms
Minimum time delay for inverse
function
(0.000–60.000) s
± 0.5% ± 25 ms
Alarm time delay
(0.00–9000.00)
± 0.5% ± 25 ms
Section 9
1MRK 502 048-UEN A
Voltage protection
284
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...