Table 41. Voltage-restrained time overcurrent protection VRPVOC
Function
Range or value
Accuracy
Start overcurrent
(2 - 5000)% of IBase
± 1.0% of I
r
at I<I
r
± 1.0% of I at I>I
r
Definite time delay
(0.00 - 6000.00) s
± 0.5% ± 25 ms
Inverse characteristics, see table
13 curve types
ANSI/IEEE C37.112
IEC 60255–151
±
3% or
±
40 ms
0.10 ≤ k ≤ 3.00
1.5 x I
set
≤ I ≤ 20 x I
set
Operate time start overcurrent
30 ms typically at 0 to 2 x I
set
20 ms typically at 0 to 10 x I
set
-
Reset time start overcurrent
40 ms typically at 2 to 0 x I
set
-
Start undervoltage
(2.0 - 100.0)% of UBase
± 0.5% of U
r
Operate time start undervoltage
30 ms typically 2 to 0 x U
set
-
Reset time start undervoltage
40 ms typically at 0 to 2 x U
set
-
High voltage limit, voltage dependent operation
(30 - 100)% of UBase
± 1.0% of U
r
Reset ratio, overcurrent
> 95%
-
Reset ratio, undervoltage
< 105%
-
Overcurrent:
Critical impulse time
Impulse margin time
10 ms typically at 0 to 2 x I
set
15 ms typically
-
Voltage protection
Table 42. Two step undervoltage protection UV2PTUV
Function
Range or value
Accuracy
Operate voltage, low and high step
(1–100)% of
UBase
± 0.5% of U
r
Reset ratio
<102%
-
Inverse time characteristics for low and high step, see table
-
Definite time delay, step 1
(0.00 - 6000.00) s
± 0.5% ± 25 ms
Definite time delays, step 2
(0.000-60.000) s
± 0.5% ±25 ms
Minimum operate time, inverse characteristics
(0.000–60.000) s
± 0.5% ± 25 ms
Operate time, start function
30 ms typically at 1.2 to 0.5U
set
-
Reset time, start function
40 ms typically at 0.5 to 1.2 xU
set
-
Critical impulse time
10 ms typically at 1.2 to 0.8 x U
set
-
Impulse margin time
15 ms typically
-
Generator protection REG650
1MRK 502 050-BEN B
Product version: 1.3
48