61
16.
Troubleshooting
16.1.
Error messages
Base Unit not responding, communication corrupted or wrong
slave address
When the HMI is not able to communicate with the Base Unit, the following
information appears on the LCD:
A051367 2
Fig. 16.1.-1
HMI is not able to communicate with the Base Unit
Solution:
Check that the Base Unit is powered and regularly working. Look at the status LED
on the connector panel (Slot X7).
The LED close to the analog inputs is related to the watchdog. When the Base Units
is working this LED is on with a weak light.
The other LED is related to the communication with the HMI. When the
communication is properly working, this LED is blinking. When the communication
is not working, the LED can be either ON or OFF. It depends on when the
communication is interrupted.
Check that the connection cable between the HMI and the Base Unit is inserted both
in the HMI and in the Base Unit (Base Unit connector X73 and HMI connector
X20) and properly tighten.
Check the slave address of the connected Base Unit to be polled. The address is
configured in the application file. If you do not know you can enter the following
page by pressing ENTER.
Multifunction Protection and Switchgear Control Unit
Operator's manual
REF 542plus
REF 542plus
1MRS755869
Summary of Contents for REF 542plus
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 18: ...18 ...
Page 20: ...20 ...
Page 24: ...24 ...
Page 28: ...28 ...
Page 34: ...34 ...
Page 40: ...40 ...
Page 44: ...44 ...
Page 70: ...70 ...
Page 72: ...72 ...
Page 84: ...84 ...
Page 114: ...114 ...
Page 116: ...116 ...
Page 126: ...126 ...
Page 132: ......
Page 133: ......