Name
Type
Description
HMICTR4
INTEGER
Bitmask output 4 to local remote LHMI input
HMICTR5
INTEGER
Bitmask output 5 to local remote LHMI input
HMICTR6
INTEGER
Bitmask output 6 to local remote LHMI input
HMICTR7
INTEGER
Bitmask output 7 to local remote LHMI input
HMICTR8
INTEGER
Bitmask output 8 to local remote LHMI input
HMICTR9
INTEGER
Bitmask output 9 to local remote LHMI input
HMICTR10
INTEGER
Bitmask output 10 to local remote LHMI input
HMICTR11
INTEGER
Bitmask output 11 to local remote LHMI input
HMICTR12
INTEGER
Bitmask output 12 to local remote LHMI input
12.4.5.3
Settings
PID-3944-SETTINGS v7
Table 194:
LOCREM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ControlMode
Internal LR-switch
External LR-switch
-
-
Internal LR-switch
Control mode for internal/external LR-
switch
PID-3943-SETTINGS v2
12.4.5.4
Operation principle
M17087-3 v8
The function block Local remote (LOCREM) handles the signals coming from the
local/remote switch. The connections are seen in Figure
function block LOCREM are connected to binary inputs if an external switch is
used. When the local HMI is used, the inputs are not used. The switching between
external and local HMI source is done through the parameter
ControlMode
. The
outputs from the LOCREM function block control the output PSTO (Permitted
Source To Operate) on Bay control (QCBAY).
1MRK 505 394-UEN A
Section 12
Control
Line differential protection RED650 2.2 IEC
359
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...