8.7.5
Settings
PID-3525-SETTINGS v8
Table 111:
CCPDSC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
tTrip
0.000 - 60.000
s
0.001
0.300
Time delay between trip condition and
trip signal
ContSel
Off
PD signal from CB
Pole pos aux cont.
-
-
Off
Contact function selection
CurrSel
Off
CB oper monitor
Continuous
monitor
-
-
Off
Current function selection
CurrUnsymLevel
0 - 100
%
1
80
Unsym magn of lowest phase current
compared to the highest.
CurrRelLevel
0 - 100
%IB
1
10
Current magnitude for release of the
function in % of IBase
Table 112:
CCPDSC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
8.7.6
Monitored data
PID-3525-MONITOREDDATA v6
Table 113:
CCPDSC Monitored data
Name
Type
Values (Range)
Unit
Description
IMin
REAL
-
A
Lowest phase current
IMax
REAL
-
A
Highest phase current
8.7.7
Operation principle
M13273-3 v6
The detection of pole discordance can be made in two different ways. If the contact
based function is used an external logic can be made by connecting the auxiliary
contacts of the circuit breaker so that a pole discordance is indicated, see figure
.
1MRK 505 394-UEN A
Section 8
Current protection
Line differential protection RED650 2.2 IEC
221
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...