132
110
3
3
kV
V
EQUATION2016 V1 EN-US
(Equation 1)
The following setting should be used:
VTprim=132
(value in kV)
VTsec=110
(value in V)
4.2.4.2
Examples how to connect, configure and set VT inputs for most
commonly used VT connections
SEMOD55055-60 v6
defines the marking of voltage transformer terminals commonly used
around the world.
A
(H1)
B
(H2)
b
(X2)
a
(X1)
A
(H1)
N
(H2)
n
(X2)
a
(X1)
b)
c)
A
(H1)
N
(H2)
dn
(X2)
da
(X1)
d)
U
Pri
+
+
U
Sec
a)
en06000591.vsd
IEC06000591 V1 EN-US
Figure 16:
Commonly used markings of VT terminals
Where:
a)
is the symbol and terminal marking used in this document. Terminals marked with a
square indicate the primary and secondary winding terminals with the same (positive)
polarity
b)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-
earth connected VTs
c)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta
connected VTs
d)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-
phase connected VTs
It shall be noted that depending on national standard and utility practices the rated
secondary voltage of a VT has typically one of the following values:
•
100 V
•
110 V
•
115 V
•
120 V
•
230 V
The IED fully supports all of these values and most of them will be shown in the
following examples.
Section 4
1MRK 505 393-UEN B
Analog inputs
56
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...