12.3.7.4
Proxy for signals from switching device via GOOSE XLNPROXY
GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1
The
SwitchType
setting controls the evaluation of the operating capability. If
SwitchType
is set to
Circuit Breaker
, the input OPCAP is interpreted as a breaker
operating capability, otherwise it is interpreted as a switch operating capability.
Table 24:
Operating capability values for breaker/switches
Value
Breaker operating capability, CbOpCap
Switch operating capability, SwOpCap
1
None
None
2
Open
Open
3
Close – Open
Close
4
Open – Close – Open
Close and Open
5
Close – Open – Close – Open
Larger values handled as 4, both Close and
Open
6
Open – Close – Open – Close – Open
7
more
tStartMove
is the supervision time for the apparatus to start moving after a
command execution is done from the SCSWI function. When the time has expired,
the command supervision is reset, and a cause-code is given.
During the
tIntermediate
time, the position indication is allowed to be in an
intermediate (00) state. When the time has expired, the command supervision is
reset, and a cause-code is given. The indication of the mid-position at SCSWI is
suppressed during this time period when the position changes from open to close or
vice-versa if the parameter
SuppressMidPos
is set to
On
in the SCSWI function.
In most cases, the same value can be used for both
tStartMove
and
tIntermediate
as
in the source function. However,
tStartMove
may need to be increased to
accommodate for the communication delays, mainly when representing a circuit
breaker.
12.4
Logic rotating switch for function selection and
LHMI presentation SLGAPC
SEMOD114936-1 v5
12.4.1
Identification
SEMOD167845-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic rotating switch for function
selection and LHMI presentation
SLGAPC
-
-
1MRK 505 393-UEN B
Section 12
Control
Line differential protection RED650 2.2 IEC
267
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...