A start of a new auto reclosing cycle during the set “reclaim time” is blocked when
the set number of reclosing shots have been reached.
12.2.2.14
External selection of auto reclosing mode
M12391-241 v5
The auto reclosing mode can be selected by use of available logic function blocks.
Below is an example where the choice of mode,
ARMode
=
3ph
or
ARMode
=
1/2/3ph
, is done from a hardware function key at the front of the IED, but
alternatively there can for example, be a physical selector switch on the front of the
panel which is connected to a binary to integer function block (BTIGAPC).
The connection example for selection of the auto reclosing mode is shown in
Figure
.
IEC14000040-1-en.vsd
IEC07000119 V3 EN-US
Figure 102:
Selection of the auto-reclose mode from a hardware functional key
in front of the IED
12.2.2.15
Auto reclosing reclaim timer
M12391-202 v4
The
tReclaim
timer defines the time it takes from issue of the breaker closing
command, until the auto recloser resets. Should a new trip occur during this time, it
is treated as a continuation of the first fault. The reclaim timer is started when the
circuit breaker closing command is given.
12.2.2.16
Pulsing of the circuit breaker closing command and counter
M12391-205 v4
The circuit breaker closing command,
CLOSECB
is given as a pulse with a
duration set by the
tPulse
setting. For circuit breakers without an anti-pumping
function, close pulse cutting can be used. It is selected by the
CutPulse
setting. In
case of a new start pulse (trip), the breaker closing command pulse is then cut
(interrupted). The minimum breaker closing command pulse length is always
50ms. At the issue of the breaker closing command, the appropriate auto recloser
operation counter is incremented. There is a counter for each type of auto reclosing
command and one for the total number of auto reclosing commands.
12.2.2.17
Transient fault
M12391-208 v4
After the breaker closing command the reclaim timer keeps running for the set
tReclaim
time. If no start (trip) occurs within this time, the auto recloser will reset.
Section 12
1MRK 505 393-UEN B
Control
238
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...