10.4.2.6
Settings
The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
10.4.3
Interlocking for busbar grounding switch BB_ES (3)
10.4.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for busbar grounding
switch
BB_ES
-
3
10.4.3.2
Functionality
The interlocking for busbar grounding switch (BB_ES, 3) function is used for one busbar
grounding switch on any busbar parts according to figure
89G
en04000504.vsd
ANSI04000504 V1 EN
Figure 131:
Switchyard layout BB_ES (3)
10.4.3.3
Function block
ANSI09000071-1-en.vsd
BB_ES (3)
89G_OP
89G_CL
BB_DC_OP
VP_BB_DC
EXDU_BB
89GREL
89GITL
BBGSOPTR
BBGSCLTR
ANSI09000071 V1 EN
Figure 132:
BB_ES (3) function block
Section 10
1MRK 511 287-UUS A
Control
280
Technical manual