Figure 135: Example of I/O-signal connections for a single-phase, two-phase or three-
phase auto reclosing sequence
Setting recommendations for multi-breaker arrangements
M12399-87 v6
Sequential reclosing in multi-breaker arrangements, like 1 1/2-breaker, double breaker and ring
bus, is achieved by giving the two line breakers different priorities. Refer to figure
. In a
single breaker arrangement the setting is
Priority = None. In a multi-breaker arrangement the
setting for the first circuit breaker, the master, is
Priority = High and for the other circuit
breaker
Priority = Low.
While the auto reclosing of the master is in progress, it issues the
WFMASTER output. After an
unsuccessful reclosing the
WFMASTER output is also maintained by the UNSUCCL signal. When
activating the
WAIT input, in the auto recloser set as slave, every dead timer is changed to the
value of setting
tSlaveDeadTime and holds back the auto reclosing operation. When the WAIT
input is reset at the time of a successful reclosing of the first circuit breaker, the slave is
released to continue the reclosing sequence after the set
tSlaveDeadTime. The reason for
shortening the time, for the normal dead timers with the value of
tSlaveDeadTime, is to give
the slave permission to react almost immediately when the
WAIT input resets. The mimimum
settable time for
tSlaveDeadTime is 0.1sec because both master and slave should not send the
breaker closing command at the same time. The slave should take the duration of the breaker
closing time of the master into consideration before sending the breaker closing command. A
setting
tWaitForMaster sets a maximum wait time for the WAIT input to reset. If the wait time
expires, the reclosing cycle of the slave is inhibited. If auto reclosing of the first breaker is
unsuccessful, the
UNSUCCL output connected to the INHIBIT input of the slave unit interrupts
the auto reclosing sequence of the latter.
1MRK 505 370-UEN D
Section 12
Control
Busbar protection REB670
279
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...