Table 17: Typical solutions for H-type stations
Version of REB670 IED
Number of differential
zones/number of
feeders per zone
Number of REB670 IEDs required for
the scheme
3PH; 2-zones, 4-bays BBP (A20)
1/4
1
3PH; 2-zones, 8-bays BBP (A31)
2/3
1
1Ph; 2-zones, 12-bays BBP (B20)
NA
NA
1Ph; 2-zones, 12-bays BBP (B21)
NA
NA
1Ph; 2-zones, 24-bays BBP (B31)
NA
NA
is given for the preconfigured versions of REB670 which do not
contain any VT inputs.
For station with double zone protection and just one set of CTs in the bus-section bay, it
might be required, depending on the client requirements, to provide the special scheme for
disconnection of bus-section CT when the bus-section CB is open. For more information, refer
to Figure
6.1.4.6
Double circuit breaker busbar arrangement
M6645-3 v5
The circuit breaker, disconnectors and instrument transformers are duplicated for every
feeder, as shown in Figure
.
QA1
BI1
BI2
QA2
QA1
BI1
BI2
QA2
QA1
BI1
BI2
QA2
QA1
BI1
BI2
QA2
QA1
BI1
BI2
QA2
ZA
ZB
xx06000018.vsd
IEC06000018 V1 EN-US
Figure 57: Example of double breaker station
This is an extremely flexible solution. In normal service all breakers are closed. The requirement
for busbar protection scheme is that the scheme must have two independent differential
zones, one for each busbar. If there is an internal fault on one of the two buses all circuit
breakers associated with the faulty busbar have to be tripped, but supply to any load will not
be interrupted. The tripping logic for the circuit breaker failure protection must be carefully
arranged.
The most common setups for this type of busbar arrangement are described in the following
table.
Table 18: Typical solutions for double circuit breaker busbar arrangement
Version of REB670 IED
Numbers of feeders
per station
Number of REB670 IEDs required for
the scheme
3PH; 2-zones, 4-bays BBP (A20)
4
2
3PH; 2-zones, 8-bays BBP (A31)
4/8
1/2
1Ph; 2-zones, 12-bays BBP (B20)
6/12
3/6
1Ph; 2-zones, 12-bays BBP (B21)
6/12
3/6
1Ph; 2-zones, 24-bays BBP (B31)
12/24
3/6
Section 6
1MRK 505 370-UEN D
Differential protection
116
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...