Technical data 57
Ambient conditions
Environmental limits for the inverter are given below.
The inverter is to be
used in indoor environment.
Note
: If the installation has ventilation ducts directly to outdoors, the back
flow of moist and dusty air must be prevented.
Operation
installed for stationary
use
Storage
in the protective
package
Transportation
in the protective
package
Installation site altitude
0 to 3000 m (9842 ft)
Above 1000 m (3281 ft),
see section
on page
-
-
Air temperature
-20 °C to +50 °C (-4 °F
to +104 °F). No
condensation allowed.
Output derated in the
range +50 °C to +60 °C
(+104 °F to +122 °F).
See section
(page
). If the
operating temperature
falls below 0 °C (32 °F),
cabinet heater option
G300 has to be used. No
frost allowed.
-40 to +70 °C
(-40 to +158 °F)
-40 to +70 °C
(-40 to +158 °F)
Relative humidity
5 to 95%
Max. 95%
Max. 95%
Environmental category
Indoor conditioned
Wet conditions
Not to be used in wet locations. The installation location must be dry.
Pollution degree
2. Normally only non-conductive pollution is allowed.
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
No conductive dust allowed.
Chemical gases:
Class 3C1
Solid particles:
Class 3S2
Chemical gases:
Class 1C2
Solid particles:
Class 1S3
Chemical gases:
Class 2C2
Solid particles:
Class 2S2
Atmospheric pressure
61.6 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Vibration
(IEC 60068-2)
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz)
sinusoidal
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz)
sinusoidal
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
max. 15 m/s
2
(49 ft/s
2
)
(9 to 200 Hz) sinusoidal
Shock
(IEC 60068-2-27)
Not allowed
Max. 100 m/s
2
(330 ft/s
2
), 11 ms
Max. 100 m/s
2
(330 ft/s
2
), 11 ms
Free fall
Not allowed
Not allowed
Not allowed
Materials
Cabinet
Hot-dip zinc-coated (thickness approximately 20 micrometers) steel sheet
(thickness 1.5 mm) with polyester thermosetting powder coating (thickness
approximately 80 micrometers) on visible surfaces except back panel.
Color: RAL 7035 (light beige, semigloss).
Air filters on the cabinet
door
AIR-TEX G-150
Busbars
Tin-plated copper or aluminum
Fire safety of materials
(IEC 60332-1)
Insulating materials and non-metallic items: mostly self-extinguishing
Summary of Contents for PVS800-57B
Page 1: ... ABB SOLAR INVERTERS PVS800 57B central inverters Hardware manual ...
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 Safety instructions ...
Page 30: ...30 Operation principle and hardware description ...
Page 32: ...32 Planning the mechanical installation ...
Page 62: ...62 Dimension drawings Cabinet dimensions ...
Page 63: ...Dimension drawings 63 ...
Page 64: ...64 Dimension drawings Cabinet attachment points ...
Page 65: ...Dimension drawings 65 ...
Page 66: ...66 Dimension drawings AC and DC cabling lead throughs ...
Page 67: ...Dimension drawings 67 ...
Page 68: ...68 Dimension drawings AC cabling ...
Page 69: ...Dimension drawings 69 ...
Page 70: ...70 Dimension drawings DC cabling ...
Page 71: ...Dimension drawings 71 ...
Page 72: ...72 Dimension drawings ...