48 Technical data
Altitude derating
The inverter load capacity (current and power) decreases if the installation site altitude is
higher than 1000 meters (3281 ft). This is due to the fact that air is thinner in higher
elevation which decreases the cooling capacity. To calculate the altitude effect for
installations at higher than 1000 m, add 0.5 °C per 100 m to the inverter temperature
derating curves (for example, an installation altitude of 1400 m adds 2 °C). When you
calculate the available inverter power, account for the different ratios of P(%) per °C at
different inverter operating temperatures (refer to
on page
).
Derating example:
This example calculation is for a site at 1600 m with an ambient temperature of 35 °C:
1. Calculate the altitude corrected temperature: 35 °C + 3 °C = 38 °C.
2. Calculate the inverter power difference with relation to the nominal (50 °C) value with
the altitude corrected temperature: (50 °C – 38 °C) * 0.8 P(%)/°C = 9.6 P(%).
3. Add the result to the inverter nominal power (100 P(%)): 100 P(%) + 9.6 P(%) =
109.6 P(%).
4. Based on the calculation, in these conditions the inverter can produce 109.6% of its
nominal power.
In the unlikely event that the total equivalent temperature (site °C + altitude °C) exceeds
the nominal temperature of 50 °C, contact ABB for information.
Summary of Contents for PVS800-57B
Page 1: ... ABB SOLAR INVERTERS PVS800 57B central inverters Hardware manual ...
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 Safety instructions ...
Page 30: ...30 Operation principle and hardware description ...
Page 32: ...32 Planning the mechanical installation ...
Page 62: ...62 Dimension drawings Cabinet dimensions ...
Page 63: ...Dimension drawings 63 ...
Page 64: ...64 Dimension drawings Cabinet attachment points ...
Page 65: ...Dimension drawings 65 ...
Page 66: ...66 Dimension drawings AC and DC cabling lead throughs ...
Page 67: ...Dimension drawings 67 ...
Page 68: ...68 Dimension drawings AC cabling ...
Page 69: ...Dimension drawings 69 ...
Page 70: ...70 Dimension drawings DC cabling ...
Page 71: ...Dimension drawings 71 ...
Page 72: ...72 Dimension drawings ...