Technical data 49
Fuses
Decrease the maximum input power in proportion to the number of unused inputs, if you
use the recommended fuse sizes and input numbers. The maximum short-circuit current
from the PV array per input is the same even if some of the inputs are not used.
Solar inverter type
PVS800-57B-1645kW-C PVS800-57B-1732kW-C
DC
DC input fuses - 16 DC inputs
• Nominal current (
I
N
)
315 A
• Quantity
32 (optionally 16)
• Max
I
SC, PV
357 A
DC input fuses - 18 DC inputs
• Nominal current (
I
N
)
250 A
• Quantity
36 (optionally 18)
• Max
I
SC, PV
317 A
DC input fuses - 20 DC inputs
• Nominal current (
I
N
)
250 A
• Quantity
40 (optionally 20)
• Max
I
SC, PV
285 A
DC input fuses - 22 DC inputs
• Nominal current (
I
N
)
200 A
• Quantity
44 (optionally 22)
• Max
I
SC, PV
259 A
DC input fuses - 24 DC inputs
• Nominal current (
I
N
)
200 A
• Quantity
48 (optionally 24)
• Max
I
SC, PV
237 A
AC
AC fuse
• Type
SC33AR5520CTF
• Body
33 screw fuse
• Nominal current (
I
N
)
2000 A
• Quantity
6
Summary of Contents for PVS800-57B
Page 1: ... ABB SOLAR INVERTERS PVS800 57B central inverters Hardware manual ...
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 Safety instructions ...
Page 30: ...30 Operation principle and hardware description ...
Page 32: ...32 Planning the mechanical installation ...
Page 62: ...62 Dimension drawings Cabinet dimensions ...
Page 63: ...Dimension drawings 63 ...
Page 64: ...64 Dimension drawings Cabinet attachment points ...
Page 65: ...Dimension drawings 65 ...
Page 66: ...66 Dimension drawings AC and DC cabling lead throughs ...
Page 67: ...Dimension drawings 67 ...
Page 68: ...68 Dimension drawings AC cabling ...
Page 69: ...Dimension drawings 69 ...
Page 70: ...70 Dimension drawings DC cabling ...
Page 71: ...Dimension drawings 71 ...
Page 72: ...72 Dimension drawings ...