Mechanical installation 69
Miscellaneous
Preventing the recirculation of hot air
Prevent hot air circulation outside the inverter by leading the outcoming hot air away from
the area where the inlet air to the inverter is taken. Also, ensure that the hot air from the
inverter module cubicle cannot enter the adjacent cubicles.
Ventilation duct at the air outlet of the cabinet
A ventilation duct can be constructed at the air outlet of the inverter cabinet. If an exhaust
fan is used, ensure that the capacity is sufficient. See
Losses, cooling data and noise
on
page
Note:
The ventilation system must keep the static pressure in the air outlet duct sufficiently
below the pressure of the room where the inverter is located in order that the cabinet fans
can produce the required air flow through the cabinet. Ensure that no dirty or moist air is
able to flow backward to the inverter in any case, even during off-time or while servicing
the inverter or the ventilation system.
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...