Technical data 133
The free space requirements are given below.
Losses, cooling data and noise
The inverter is cooled by an internal fan, flow direction from front to top.
1)
for dimensioning the ventilation of the electric equipment room
2)
cooling air flow for a cabinet with one DC input cubicle only
3)
at partial power typically < 65 dB with speed-controlled fans
Terminal and lead-through data for the DC input power
cable
The DC busbars are tin-plated. Cable lugs suited to tin-plated materials can be used.
Required free space around the unit for cooling
Front
Side
Above
Back
mm
in.
mm
in.
mm
in.
mm
in.
150
5.91
-
-
500
19.68
-
-
Required free space for door opening
.
Inverter type
Heat dissipation
1)
Cooling air flow
Noise
Inverter module cubicles
Total air flow
2)
kW
m
3
/h
ft
3
/h
m
3
/h
ft
3
/h
dB
PVS800-57-0100kW-A
4
-
-
1300
46000
75
PVS800-57-0250kW-A
10
2500
88300
3250
115000
75
3)
PVS800-57-0315kW-B
10
2500
88300
3250
115000
75
3)
PVS800-57-0500kW-A
20
5000
177000
6000
212000
75
3)
PVS800-57-0630kW-B
20
5000
177000
6000
212000
75
3)
PVS800-57-0875kW-B
30
7950
281000
9450
333700
75
PVS800-57-1000kW-C
30
7950
281000
9450
333700
75
Inverter type
No. of cable lead-throughs Ø60 mm (2.36”)
+H377
+H382
+2/4/5H382
+8/10H382
+12/16/20H382
PVS800-57-0100kW-A
3 × 3
1 × 3
-
-
-
-
PVS800-57-0250kW-A
-
-
4 × 4
8 × 4
-
-
PVS800-57-0315kW-B
-
-
4 × 4
8 × 4
-
-
PVS800-57-0500kW-A
-
-
4 × 4
8 × 4
12 × 4
-
PVS800-57-0630kW-B
-
-
4 × 4
8 × 4
12 × 4
-
PVS800-57-0875kW-B
-
-
-
8 × 4
12 × 4
16 x 4
PVS800-57-1000kW-C
-
-
-
8 × 4
12 × 4
16 x 4
IP54
> 500 mm
(19.68 in.)
> 400 mm
(15.75 in.)
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...