Quickstart
Chapter 2
18
1SFC132003M0201
2:2
Configuration
1. Enter the Application Setting by pressing left selection key
twice. Press
Select
using the left selection key. Figure 4.
2. Select the appropriate type of load using navigation keys.
3. Press
Store Set
and
Nex
t to continue or
Back
to previous
parameter using the selection keys. Figure 6.
4. Set the Setting Ie using the navigation keys.
In Line connected = rated motor current
inside Delta connected = 58% (
) of the rated
motor Icurrent. Figure 7.
5. Press
Store
and
Next
to continue or
Back
to previous
parameter using the selection keys. Figure 8.
6. Set the required overload class using the navigation keys.
7. Press
Store
and
Next
to continue or
Back
to previous
parameter using the selection keys. Figure 10.
8. If an external by-pass contactor is used set
Ext ByPass
to
Yes
using the navigation keys. (PST30...300 only).
9. Press
Store
and
Next
to continue or
Back
to return to pre-
vious parameter using the selection keys. Figure 12.
10.Select
Yes
if ready or
Tune Set
if start/stop mode, ramp
types, initial/end voltage, current limits etc. needs to be
adjusted using selection keys. Figure 13.
11.To change presentation language, see section 7:2.5.
2:3
Start of the motor
1. Switch on the main voltage.
2. Give start command to the softstarter.
(To start the softstarter from the keypad, enter the LOCAL
CONTROL menu, select
Start/Stop,
and press
Start
. The
motor must be stopped before leaving this menu.)
Application Setting
Select
Back
Figure 4: Application setting menu
Centrifugal
Pump
Store Set
Back
Figure 5: Centrifugal pump
Centrifugal
Pump
Next
Back
Figure 6: Centrifugal pump stored
1
3
(
)
⁄
Setting Ie
99.0A
Store
Figure 7: Setting Ie
Setting Ie
99.0A
Next
Back
Figure 8: Setting Ie stored
OL Class
10
Store
Figure 9: OL Class
OL Class
10
Next
Back
Figure 10: OL class stored
Ext ByPass
No
Store
Figure 11: External Bypass
Ext ByPass
No
Next
Back
Figure 12: External Bypass stored
Ready?
Yes
Tune Set
Figure 13: Ready / Tune Set
Summary of Contents for PST30
Page 2: ...This manual belongs to...
Page 4: ......
Page 8: ...Chapter 8 1SFC132003M0201 Notes...
Page 10: ...Introduction 10 1SFC132003M0201...
Page 14: ...Introduction Chapter 1 14 1SFC132003M0201...
Page 16: ...Quickstart 16 1SFC132003M0201...
Page 20: ...Description 20 1SFC132003M0201...
Page 34: ...Description Chapter 3 34 1SFC132003M0201...
Page 36: ...Mounting 36 1SFC132003M0201...
Page 40: ...Mounting Chapter 4 40 1SFC132003M0201...
Page 42: ...Connection 42 1SFC132003M0201...
Page 60: ...Connection Chapter 5 60 1SFC132003M0201...
Page 62: ...Human Machine Interface HMI 62 1SFC132003M0201...
Page 74: ...Human Machine Interface HMI Chapter 6 74 1SFC132003M0201...
Page 76: ...Setting and configuration 76 1SFC132003M0201...
Page 120: ...Fieldbus communication option 120 1SFC132003M0201...
Page 124: ...Maintenance 124 1SFC132003M0201...
Page 126: ...Maintenance Chapter 9 126 1SFC132003M0201...
Page 130: ...Chapter 130 1SFC132003M0201...
Page 178: ...Trouble shooting 178 1SFC132003M0201...
Page 188: ...Trouble shooting Chapter 11 188 1SFC132003M0201...
Page 190: ...Diagrams 190 1SFC132003M0201...
Page 199: ......