Trouble shooting
Chapter 11
182
1SFC132003M0201
Frequency fault
The frequency is out of range.
(47.5 - 52.5Hz or 57 - 63Hz)
• Check and correct the frequency.
Line side fault
The main voltage is not correct
on the line side.
• Check and correct voltage on the line
side.
Heat sink over-temperature
fault
Temperature too high on the
heat sink. If the fault remains
after reset, the heat sink temper-
ature is too warm.
• Check that the fans are working in a
proper way.
• Check that cooling airways are free from
dirt and dust.
• Check that the ambient temperature is
not too high.
Kick-current fault
Parameter
Setting I
e
is set too
low.
In Line connected
• Set the value according to the rated
motor current.
Inside Delta
• Set the value according to 58%
(
) of the rated motor current.
Thyristor short circuit fault
One or several SCRs are
shorted.
• Check and replace. Contact your ABB
sales office for replacement kit.
Non conducting thyristor
One or several SCRs are not
conducting.
• Check and replace. Contact your ABB
sales office for replacement kit.
Status
Possible cause
Solution
Power on
Protection
Fault
Fault Wrong Freq
Reset
Back
Power on
Protection
Fault
Fault Line Side
Reset
Back
Power on
Protection
Fault
Fault HS Temp
Reset
Back
Power on
Protection
Fault
Fault Kick-Cur
Reset
Back
1
3
(
)
⁄
Power on
Protection
Fault
Fault SC SCR
Reset
Back
Power on
Protection
Fault
Fault Open SCR
Reset
Back
Summary of Contents for PST105
Page 2: ...This manual belongs to ...
Page 4: ......
Page 8: ...Chapter 8 1SFC132003M0201 Notes ...
Page 10: ...Introduction 10 1SFC132003M0201 ...
Page 14: ...Introduction Chapter 1 14 1SFC132003M0201 ...
Page 16: ...Quickstart 16 1SFC132003M0201 ...
Page 20: ...Description 20 1SFC132003M0201 ...
Page 34: ...Description Chapter 3 34 1SFC132003M0201 ...
Page 36: ...Mounting 36 1SFC132003M0201 ...
Page 40: ...Mounting Chapter 4 40 1SFC132003M0201 ...
Page 42: ...Connection 42 1SFC132003M0201 ...
Page 60: ...Connection Chapter 5 60 1SFC132003M0201 ...
Page 62: ...Human Machine Interface HMI 62 1SFC132003M0201 ...
Page 74: ...Human Machine Interface HMI Chapter 6 74 1SFC132003M0201 ...
Page 76: ...Setting and configuration 76 1SFC132003M0201 ...
Page 120: ...Fieldbus communication option 120 1SFC132003M0201 ...
Page 124: ...Maintenance 124 1SFC132003M0201 ...
Page 126: ...Maintenance Chapter 9 126 1SFC132003M0201 ...
Page 130: ...Chapter 130 1SFC132003M0201 ...
Page 178: ...Trouble shooting 178 1SFC132003M0201 ...
Page 188: ...Trouble shooting Chapter 11 188 1SFC132003M0201 ...
Page 190: ...Diagrams 190 1SFC132003M0201 ...
Page 199: ......