1SFC132005C0201, rev.F | Softstarters 45
PST(B) – The advanced range
Technical data
PSTB Integrated by-pass ratings
Softstarter
PSTB370
PSTB470
PSTB570
PSTB720
PSTB840
PSTB1050
Integrated contactor
AF300
AF460
AF580
AF750
AC-3 rating (A)
305
460
580
750
Rated insulation voltage U
i
690 V
Control circuit
Rated operational voltage U
e
208...600 V, 400...690 V + 10 % / -15 % 50/60 Hz ±5%
Number of inputs
2 (start, stop)
Rated control supply voltage U
s
100...250 V +10% / -15% 50/60 Hz ±5%
Number of additional
programmable inputs
2
(Each input can be programmed to
be either; Non, Reset, Enable, Jog,
DOL- On, Start motor 2, Start motor 3
or FB-Dis)
Rated control circiut voltage U
c
Internal or external 24 V DC
Starting capacity at I
e
4 x I
e
for 10 sec.
Number of starts per hour
PST30...300
PSTB370...1050
30
1)
10
1)
Signalling indication LED
Overload capability
Overload class
10
Power on
Green
Fault
Red
Service factor
PST(B)30...840
PSTB1050
Protection
Yellow
115 %
100 %
Ambient temperature
Protections
during operation
±0 ... +50 °C
2)
during storage
-25 ... +70 °C
Electronic overload
Yes
(Class 10A, 10, 20, 30)
Dual overload
Yes
(separate overload function for
start and run)
Maximum altitude
4000 m
3)
Degree of protection
PST30...72
PST85...PSTB1050
PTC connection
Yes
main circuit
IP10
IP00
Locked rotor protection
Yes
(Level and delay adjustable)
Supply and control circuit
IP20
Underload protection
Yes
(Level and delay adjustable)
Main circuit
PST30...300
PSTB370...1050
Phase imbalance
Yes
(Level and delay adjustable)
Built-in By-pass contactor
No
Yes
High current (8 x I
e
)
Yes
Cooling system - Fan cooled
Yes
(thermostat controlled)
Phase reversal protection
Yes
HMI for settings
(Human Machine Interface)
Warnings (pre-warning)
Display
Full text
High current
Yes
(Level and delay adjustable)
Languages
English, German, Italian, Dutch, Chinese, Finnish,
Low current (underload)
Yes
(Level and delay adjustable)
Swedish, French, Spanish, Russian, Portugese,
Overload trip
Yes
(Level and delay adjustable)
Turkish, Polish and Czech
Overtemp, thyristor (SCR)
Yes
Keypad
2 selection keys and 2 navigating keys
Start of several motors
Signal relays
Possible to set-up and start three Yes
(Different parameter sets)
Number of programmable
3 (each relay can be programmed to be
different motors
signal relays
Run, By-pass or Event signal)
Field bus connection
K4
Default as Run signal
Connection for ABB FiledBus Plug Yes
K5
Default as TOR (By-pass) signal
PTC input
K6
Default as Event signal
Switch off resistance
2825 ohm ± 20%
Rated operational voltage, U
e
250 V AC / 24 V DC
Switch on resistance
1200 ohm ± 20%
Rated thermal current I
th
5 A
External keypad
Rated operational current I
e
at
1.5 A
Display
LCD type
AC-15 (U
e
=250 V)
Ambient temperature
Analog output
During operation
±0 ... +50 °C
Output signal reference
0 ... 10 V, 0 ... 20 mA, 4 ... 20 mA
During storage
-25 ... +70 °C
Type of output signal
I Amp, U Volt, P kW, P hp, Q kVAr, S kVA, TmpMot,
TmpSCR, cosPhi
Degree of protection
IP66
1)
Valid for 50 % on time and 50 % off time. If other data is required, contact your sales office.
2)
Above 40 ºC up to max. 50 ºC reduce the rated current with 0.8 % per ºC.
3)
When used at high alitudes above 1000 meters up to 4000 meters you need to derate the rated current using the following formula.
[ % of I
e
= 100 - x - 1000 ] x = actual altitude for the softstarter
150