54 Parameters
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
130 Limits
130.01
Limit word 1
Shows active power limitation status.
-
b0...b1: Reserved
Reserved
b2: P max
Maximum power level
b3: P min
Minimum power level
b4: Reserved
Reserved
b5: Power gradient
Power gradient
b6: Stop ramp
Stop ramp
b7: P(f)
P(f) limitation
b8: Grid fault
Power is limited after grid fault.
b9: Connect
Power is limited after connection to grid.
b10: External
External limit is active,
.
b11: FRT recovery
Power is limited after FRT event.
b12: P(U)
P(U) limitation
b13: Flat-top
Flat-top
b14: Input current
Input current
b15: Grid current
Grid current is limiting active power.
130.02
Limit word 2
Shows reactive power limitation status.
-
b0: Q ref max
Reactive power reference is limited by
b1: Q ref min
Reactive power reference is limited by
.
b2...b14: Reserved
Reserved
b15: Current
Grid current is limiting reactive power.
130.04
Limit word 4
Shows current based limitation status.
-
b0...b1: Reserved
Reserved
b2: I max
Maximum current
b3: CB temperature
Control board temperature
b4: Inverter temperature
IGBT temperature
b5: Filter temperature
Line filter temperature
b6: Nominal power
Nominal apparent power
b7...b15: Reserved
Reserved
130.62
P(f) limit type
Selects the P(f) limiter type.
Disabled
Disabled
P(f) limiter is disabled.
0
Free running
Limit moves both ways along the gradient.
1
Incremental
Limit only decreases along the gradient until the
frequency drops below the corner point
2
130.63
P(f) corner frequency
Sets the starting point for limitation.
50.2 Hz
40 … 70 Hz
100 = 1 Hz
130.64
P(f) limit gradient
Sets the limit gradient.
40%/Hz
0 … 200%/Hz
10 = 1%/Hz
130.65
P(f) release frequency
Sets the frequency where the power limit is
released and ramping the limit up starts.
50.2 Hz
40 … 70 Hz
100 = 1 Hz
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...