Program features 27
Limitation based on grid voltage
Active power limit as a function of grid voltage is used to counteract the increase in grid
voltage due to active power production. When average grid voltage
•
exceeds
, the power limit is ramped down to
. Parameter
defines the slope of the ramp down from the
P(U) triggering level.
•
, power limit is released and active power
ramps upwards as defined by parameter
Settings
130.81 P(U) Release ramp
130.80 P(U) Limit ramp
130.79 P(U) Limit level
P
t