20 Program features
Connection limits
The grid monitoring function of the inverter includes a connection condition checking that
is used only in a grid connection. Typically, the connection limits are stricter than the
disconnection limits. The connection limits are also referred as "cut-in" conditions.
There are connection limits for underfrequency, overfrequency, overvoltage and
undervoltage. Each phase/main voltage is independently monitored.
Settings
Voltage monitoring
There are two limits for undervoltage monitoring and three limits for overvoltage
monitoring. Each limit has an enable parameter, a limit parameter and a time parameter.
When the limit is enabled and the measured value exceeds the limit for the time, the grid is
declared as unstable. All limits are logically connected in parallel. Each phase/main
voltage is independently monitored.
Settings
Sliding overvoltage
Sliding overvoltage implements the monitoring of the slowly rising AC voltage. A
10 minutes average value is calculated and compared against the limit. Each phase/main
voltage is independently monitored.
Settings
Frequency monitoring
There are two limits for underfrequency and overfrequency monitoring. Both the limits
have an enable parameter, a limit parameter and a time parameter.
When the limit is enabled and the measured value exceeds the limit for the time, the grid is
declared as unstable. All limits are logically connected in parallel.
Settings
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...