![ABB PRO-33.0-TL Series Service Manual Download Page 91](http://html.mh-extra.com/html/abb/pro-33-0-tl-series/pro-33-0-tl-series_service-manual_3045376091.webp)
Parameters 91
188.32
Underfrequency time 1
Sets trip time for underfrequency protection.
100 ms
0 ... 120 000 ms
1 = 1 ms
188.33
Underfrequency enable 2
Enables underfrequency protection.
1
0 ... 1
1 = 1
188.34
Underfrequency limit 2
Sets limit for underfrequency protection.
-1 Hz
-30 ... 0 Hz
1 = 1 Hz /
10 = 1 Hz
188.35
Underfrequency time 2
Sets trip time for underfrequency protection.
100 ms
0 ... 120 000 ms
1 = 1 ms
188.40
Overfrequency enable 1
Enables overfrequency protection.
1
0 ... 1
1 = 1
188.41
Overfrequency limit 1
Sets limit for overfrequency protection.
1 Hz
0 ... 30 Hz
1 = 1 Hz /
10 = 1 Hz
188.42
Overfrequency time 1
Sets trip time for overfrequency protection.
100 ms
0 ... 120 000 ms
1 = 1 ms
188.43
Overfrequency enable 2
Enables overfrequency protection.
1
0 ... 1
1 = 1
188.44
Overfrequency limit 2
Sets limit for overfrequency protection.
1 Hz
0 ... 30 Hz
1 = 1 Hz /
10 = 1 Hz
188.45
Overfrequency time 2
Sets trip time for overfrequency protection.
100 ms
0 ... 120 000 ms
1 = 1 ms
188.50
Undervoltage enable 1
Enables undervoltage protection.
1
0 ... 1
1 = 1
188.51
Undervoltage limit 1
Sets limit for undervoltage protection.
80
0 ... 100%
1 = 1
188.52
Undervoltage time 1
Sets trip time for undervoltage protection.
100 ms
0 ... 120 000 ms
1 = 1 ms
188.53
Undervoltage enable 2
Enables undervoltage protection.
0
0 ... 1
1 = 1
188.54
Undervoltage limit 2
Sets limit for undervoltage protection.
80%
0 ... 100%
1 = 1%
188.55
Undervoltage time 2
Sets trip time for undervoltage protection.
0 ms
0 ... 120 000 ms
1 = 1 ms
188.63
Overvoltage enable 1
Enables overvoltage protection.
1
0 ... 1
1 = 1
188.64
Overvoltage limit 1
Sets limit for overvoltage protection.
110
100 ... 200%
1 = 1
188.65
Overvoltage time 1
Sets trip time for overvoltage protection.
100 ms
0 ... 120 000 ms
1 = 1 ms
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...