Program features 15
DC voltages and maximum power point tracking
The following picture visualizes the operational voltage ranges of the PRO-33.0.-TL
inverter. The input operation voltage range depends on the AC voltage and it is between
580 and 950 volts when the AC voltage is nominal 400 V
AC
.
•
MPPT range @ P
AC, rated
= maximum power available with tracking, no derating
•
MPPT range = maximum power tracking range, power may be derated.
•
Start range = Input voltage range where inverter may start
Start range
The inverter starting range is between 610 V and 1000 V. The minimum startup voltage
depends linearly on AC voltage. 610 V is valid at nominal AC voltage 400 V
AC
. If the
voltage at start is greater than 950 V, it is regulated down to 950 V where tracking is
started.
5
Available power is less than the inverter’s power limit
P
act
< P
lim
6
Inverter disabled (parameter
OR
fault
OR
grid unstable
OR
VDC low
OR
VDC > VDC
max
OR
FRT overshoot
7
No monitoring mode (parameter
)
AND
VDC < VDC
sleep
AND
Control unit screensaver active
AND
No events active
8
Inverter disabled (parameter
OR
fault
OR
grid unstable
OR
VDC < VDC
start
Warning ”DC
overvoltage”
Grid
connection is
not allowed.
Fault ”DC
overvoltage”
Inverter may be
damaged.
P
max
U
Derating
range
Forbidden area
Non-operating
range
Start range
Vmax = 1100 V
550 V
580 V
610 V
Vmppt,max
850 V
Vdc,ref,max
950 V
Vmax,operating
1000 V
Par 178.4 MPPT Voltage max
VDC start@ VAC= 400 V
Vmppt min@ VAC > 400 V
Vmppt min@ VAC = 400 V
Vmppt min@ VAC < 400 V
MPPT range
MPPT range @ P
AC, rated
Par 178.3 MPPT Voltage Min
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...