Installation requirements 37
Power cable requirements
Select the DC and AC cables according to the local regulations and the following
rules:
• Use cables that are rated for at least 70 °C maximum permissible temperature of
conductor in continuous use.
• Use double-insulated DC cables.
• Use a DC cable that is rated for at least 1,000 V
DC
and which is approved for
photovoltaic applications. If the PV system voltage exceeds 1,000 V, select the
DC cable according to the system voltage.
• Use an AC cable that is rated for at least 500 V
AC
.
• The AC cable must have either L1, L2, L3, N and PE or L1, L2, L3 and PE
conductors. Obey the local regulations.
• You can use copper and aluminium AC cables.
• Dimension the AC cables to carry the inverter load current with a maximum
voltage drop of 1% between the inverter and the AC distribution board.
• Connect the PE conductor primarily to the AC connector.
• The minimum permitted PE conductor cross-sectional area is 10 mm
2
for a
copper (Cu) conductor. If the cable has a smaller PE conductor, connect an
additional PE conductor of at least 6 mm
2
with a cable lug to the auxiliary PE
terminal of the inverter.
• (-SX model) Use Phoenix Contact SUNCLIX PV quick connectors:
DC+: PV-CF-S (1774674)
DC-: PV-CM-S (1774687)
Recommended AC output cable types
The outer diameter of the AC output cable must be 22…32 mm (0.9…1.2 in.).
With the supplied reducer seal for the cable gland, the outer diameter can be
14...26 mm (0.6…1.0 in.).
Maximum recommended AC cable lengths
per nominal output power
(based on 1% maximum AC cable losses)
Conductor (Cu)
cross-section
33,000 W
48 A
rms
mm
2
AWG
m
ft
10
7
23
75
16
5
36
118
25
3
57
187
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Hardware description ...
Page 40: ...40 Installation requirements ...
Page 70: ...70 Electrical installation ...
Page 74: ...74 Installation checklist ...
Page 110: ...110 Maintenance ...
Page 134: ...134 Navigation map The navigation map ...
Page 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...