Installation requirements 35
Photovoltaic array and inverter compatibility
Make sure that:
• The PV modules and DC cables are Protection Class II certified (double
insulated).
• The PV modules are not grounded to the DC+ or DC- terminals.
• The PV modules are of the same type and that they have a IEC 61730 Class A
rating.
• The PV strings have an equal configuration for optimized energy output.
• The PV string and array maximum short-circuit currents and open-circuit voltages
for DC inputs match the rated values of the inverter under local ambient
conditions. Refer to
on page
.
• The PV array operating voltage range is in the MPPT voltage range at all ambient
temperatures. Refer to
on page
. The string voltage tends to
increase in low ambient temperatures.
• The -SX model is equipped with 15 A string fuses (refer to
on page
for fuse types). Make sure that the 15 A string fuses are sufficient and
compatible with the PV array design and installation materials. The nominal
current of the string fuses is defined at 25 °C. Take into account the possible
temperature deviations when you select fuses.
String fuse nominal current rating
I
FN
• Read the nominal short-circuit current
I
SC
rating from the data sheet of the PV
module.
• Read the maximum allowed series fuse rating or reverse current rating
I
R
from the
data sheet of the PV module.
• Define the conductor current carrying capacity
I
C
of the used string cable type in
the planned installation conditions.
• The correct nominal current rating
I
FN
of the string fuse in the planned installation
conditions:
I
FN
> 1.56 ×
I
SC
I
FN
≤
I
R
or if
I
R
is not specified in module data sheet
I
FN
< 2 ×
I
SC
I
FN
≤
I
C
When you use this formula to select the fuses, take into account the factors that
can cause adjustments to the formula:
•
The thermal derating of the fuse.
•
The effective radiation at the installation site.
•
The PV module
I
sc
temperature dependence at the site.
•
The maximum return current of the PV modules.
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Hardware description ...
Page 40: ...40 Installation requirements ...
Page 70: ...70 Electrical installation ...
Page 74: ...74 Installation checklist ...
Page 110: ...110 Maintenance ...
Page 134: ...134 Navigation map The navigation map ...
Page 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...