Tension Electronics PFEA113, User Manual
Chapter 3 Commissioning
3-20
3BSE029382R0101 Rev C
Figure 3-10. Three PFEA113 Connected to Segmented Roll with 12 (max.) Load Cells
Connecting Multiple Electronics (two or three PFEA113 connected together)
Analog inputs AI1 and AI2, see
, are used for connecting two or three PFEA113
electronics together. The configuration example below is based on
If N/m, kN/m, kg/m or pli is chosen as presentation unit, the total web width must be entered in
all three electronics.
The same wrap gain value must be entered in all three electronics.
If the scale factor SRSF is used, the SRSF must be calculated and set separately for each
electronic unit, see also
Appendix A.3 Technical Data for Tension Electronics PFEA113
1.
Configuration rules for analog outputs(AO) on PFEA113 (1) and PFEA113 (2) to be
connected to AI1 and AI2 on PFEA113 (3):
–
Choose voltage output, since AI1 and AI2 can only be connected to voltage signals.
–
Use the
ConnectSignals
alternative that includes the load cell signals you want to
connect to the output, see
.
–
Set the filter settings to 5 ms (the shortest selectable time).
–
Set
HighTension
(N, kN, kg, lbs, N/m, kN/m, kg/m or pli) and
HighOutput
(V).
2.
Configuration rules for the AI1 and AI2 on PFEA113 (3)
–
Set
HighTension
(N, kN, kg, lbs, N/m, kN/m, kg/m or pli) of AI1 =
HighTension
of
PFEA113 (1).
–
Set
HighInput
(V) of AI1 =
HighOutput
(V)
of PFEA113 (1).
–
Set
HighTension
(N, kN, kg, lbs, N/m, kN/m, kg/m or pli) of AI2 =
HighTension
of
PFEA113 (2).
–
Set
HighInput
(V) of AI2 =
HighOutput
(V)
of PFEA113 (2).
3.
Configuration rules for the output (used for summation) on PFEA113 (3)
–
Choose voltage output or current output.
–
Use the
ConnectSignals
alternative that includes all signals you want to connect to
the summation output, see
–
Set the desired filter settings.
Note!
If the Step Response time is set to 5 ms and analog inputs (AI1 and/or AI2) are
included in the summation output the filter settings will increase to 6 ms.
Segmented Roll
(11 roll segments) with the maximum number of load cells (12) connected
A1
B1
C1
D1
A2
B2
C2
D2
A3
B3
C3
D3
A3
B3
PFEA113 (3)
C3
D3
A1
B1
PFEA113 (1)
C1
D1
A2
B2
PFEA113 (2)
C2
D2
AI1
AI2
A2+B2+C2+D2
A1+B1+C1+D1
A3+B3+C3+D3
Web Tension
+ AI1 + AI2
AI1
AI2
AI1
AI2
Voltage output
(voltage or
current output)
must be used
Voltage output
must be used
(used for summation)
Not used
Not used
Not used
Not used
Summary of Contents for PFEA 113
Page 32: ...Tension Electronics PFEA113 User Manual Chapter 2 Installation 2 16 3BSE029382R0101 Rev C ...
Page 92: ...Tension Electronics PFEA113 User Manual Chapter 5 Maintenance 5 2 3BSE029382R0101 Rev C ...
Page 104: ...Tension Electronics PFEA113 User Manual Chapter 6 Fault tracing 6 12 3BSE029382R0101 Rev C ...
Page 259: ......