Menu 700 Charger Settings
700 Charger Settings
Parameter:
710 Charging Mode
Function:
Sets which chargers will operate
Range:
None, Float, Module, Both
Factory
Setting:
Both
Access:
Tech
Parameter:
711 Charging Current
Function:
Sets the current level during charging
Range:
0 to 40%
Units:
% of the PCS100 UPS-I rated current
Factory
Setting:
10% for battery systems, 20% for Ultracapacitors
Access:
Factory
Note:
Because charging feeds power into the energy storage (Ultracapacitors or batteries)
which have low impedance the inverters are current controlled and the accuracy of the
current may be reduced.
Parameter:
715 Force Float Charger On
Function:
Forces the Float Charger on.
Range:
0 to 60
Units:
Minutes
Factory
Setting:
0
Access:
Tech
Note:
This should only be used to assist maintenance work, such as when measuring battery
balance or reconnecting a discharged capacitor enclosure.
Table 10
-
9: Menu 700 Charger Settings