OVRHLD SERIES

  SU R G E  P R OT EC T I V E  D E V I C E S

 

WARNING!: 

THE OVRHLD SERIES WARRANTY IS VOIDED if the 
unit is damaged as a result of improper installation 
or the installer’s failure to verify the following 
conditions prior to installation.

 

WARNING!: 

HAZARDOUS VOLTAGES PRESENT: Improper 
installation or misapplication may result in serious 
personal injury or damage to the electrical system. 
Read the complete installation instructions before 
proceeding with installation. Remove all power to 
the electrical panel before installing or servicing 
the SPD.

 

WARNING!: 

IMPORTANT SAFETY INSTRUCTIONS: All work must 
be performed by licensed and qualified personnel. 
Follow applicable electrical specifications for the 
country the unit is being used in.

 

WARNING!: 

Do not HIPOT the OVRHLD series units or the 
electrical system to which the OVRHLD series unit 
is connected without disconnecting the OVRHLD 
series units conductors including phases, neutral 
and ground.

Warning!  
lnstallation by person with electrotechnical 
expertise only.

Warnung!  
lnstallation nur durch elektrotechnische Fachkraft.

Avertissement! 
lnstallation uniquement par des personned 
qualifiées électrotechnique.

iAdvertencia!  

La instalación deberá ser realizada únicamente por 
electricistas especializados.

This manual provides guidelines for the proper 
installation of the OVRHLD series of devices. Proper 
product selection and compliance with these 
guidelines will help your new suppression system 
provide years of reliable service. If installers are 
unsure about the facility electrical configuration 
or have other installation-related questions, it 
is recommended they consult with a qualified 
electrical professional.

When shortcuts are taken or installation procedures 
are not followed, the OVRHLD series may become 
damaged or may not provide adequate protection. 
It is extremely important to follow these installation 
procedures carefully.

Guide to installation and assistance

Thank you for choosing the ABB OVRHLD series Surge Protective Device (SPD). 
We look forward to fulfilling your facilitywide surge protection needs.

Summary of Contents for OVRHLD Series

Page 1: ... PRODUCT MANUAL OVRHLD Surge protective devices Installation operation and maintenance manual ...

Page 2: ...gned for protection of downstream distribution equipment and wiring as well as most sensitive electrical and electronic loads from the effects of overvoltage transients that might result from lightning induction and switching of loads or capacitor banks This is a light duty device and should be used in minimum to moderate lightning environments or in high lightning areas if used downstream of a pr...

Page 3: ...________________________________________________________ Date of purchase _____________________________________________________________________________________ Date installed _____________________________________________________________________________________ Installer _____________________________________________________________________________________ ...

Page 4: ...d ground Warning lnstallation by person with electrotechnical expertise only Warnung lnstallation nur durch elektrotechnische Fachkraft Avertissement lnstallation uniquement par des personned qualifiées électrotechnique iAdvertencia La instalación deberá ser realizada únicamente por electricistas especializados This manual provides guidelines for the proper installation of the OVRHLD series of dev...

Page 5: ...door or outdoor If installed outdoors in hot climates avoid direct sun exposure Orient the unit so the functional status lights are visible This unit cannot be employed on a flush mounted load center with a finished wall surface Connection Mount through 1 2 knockout 12 7 mm in the electrical panel and secure with lock nut Black wires connect to phase hot white wire to neutral bar green yellow wire...

Page 6: ...Optimum application location OVRHLD yy xxx 1 L1 N N G 1 LED 2 or 4 wire branch circuit local lightning conditions OVRHLD yy xxx 2 L1 N L2 N 2 LEDs 3 or 4 wire service entry OVRHLD yy xxx 3 L1 G L2 G 2 LEDs 3 wire L L branch circuit w o neutral connected loads OVRHLD yy xxx 4 L1 G N G 1 LED 2 wire incoming branch circuit common mode lightning protection OVRHLD yy xxx 5 L1 N L1 G 2 LEDs 2 wire branc...

Page 7: ...LD xx yyy 3 4 wire circuits 3 wire circuits OVRHLD xx yyy 1 For three phase circuits 120 208 220 380 230 400 240 415 and 277 480 OVRHLD xx yyy 2 For single phase voltages where L N could be 120 230 or 277 For split single phase and 2 legs off a Wye circuits L N at 120 230 or 277 Service may be 120 240V 1 phase 3 wire or 208Y 120V 2 phase 3 wire Electrical connections G N L G N L EARTH GROUND SPD E...

Page 8: ...appear in this document We reserve all rights in this document and in the information contained therein Without prior written approval from ABB reproduction disclosure to third parties or use of any information in whole or in part is strictly forbidden Electrification Products 5900 Eastport Boulevard Richmond VA 23231 4453 USA Tel 1 800 292 3739 Fax 1 804 236 4047 abb com Copyright 2017 Thomas and...

Reviews: