OVR 

 Three phase mechanically ganged reclosers 

Operator’s

 quick reference guide for OVR-15, OVR-27 & OVR-38

 

Page 

of 

 

 

 

2.

 

LED indication on ACU 

LED Status 

Description

 

 

 

 

 

 

 

 

 

 

 

C.

 

Switches on relay front fascia 

 

 

D.

 

Handling reclosers during long outages 

 

1.

 

Recloser needs auxiliary power for general application. This power is generally derived from the distribution feeder itself 

with the help of control transformer or fed from substation auxiliary source. In case of temporary unavailability of auxiliary 

power (few hrs. in a day), the recloser is feed via internal battery bank of the LV cabinet. 

2.

 

If battery bank is healthy and in fully charge condition i.e. 

≥ 

24 Vdc, for the power outage can be of < 24Hrs. without any 

special attention required. 

3.

 

If power outage is for more than 24 Hrs OR typically > 10 CO operations after power failure, then it is considered as long 

power outage requiring special attention of batteries. 

4.

 

During long outages, the batteries might get drained to such a level that it might go into deep discharge stage i.e. battery 

bank voltage goes below 18 V. 

5.

 

In this situation recloser will not be able to recharge the batteries automatically and external charging may be required. 

Such situation might also damage batteries permanently and thus required to be replaced. 

6.

 

To avoid such situation, in case of power outage more than 24 Hrs. switch OFF the battery MCB D10-24. After the power is 

resume, switch ON the battery MCB D10-24 

7.

 

If power outage is more than a month, then charge the batteries on regular interval externally to keep ensure the battery 

bank voltage more than 21 VDC. 

1

 

2

 

3

 

4

 

 

OFF

 

Blinking

 

fast

 

OFF

 

OFF

 

Normal condition 

 ACU ready to

 

perform operations

 

Blinking

 

slowly

 

Blinking

 

fast

 

OFF

 

OFF

 

Close operation is not allowed

 

ON

 

Blinking

 

fast

 

OFF

 

OFF

 

Both open and close operations are

 

not allowed

 

Don’t

 care 

Blinking slowly  Boot loader started but the FW is

 

missed

 

ON

 

OFF

 

ON

 

OFF

 

File system error

 

OFF

 

OFF

 

ON

 

ON

 

Initial condition at start-up

 

If the LEDs remain in this condition,

 

the CPI has not started

 

ON

 

ON

 

ON

 

ON

 

This state shows for 3 seconds 

indicating ACU can receive FW

 

upgrades

 

 