7) Check voltage presence.
The metal OneFit door still provides a metal
partition but the large window enables to
access the cable test truck terminals for
voltage presence verification with proper
insulating high voltage tester. Check the rating
of the insulating high voltage tester is
adequate to the equipment voltage class.
Check voltage presence on each phase
terminals with a proper high voltage tester
and PPE (Personal Protective Equipment).
Check each phase.
Figure 18b. HV presence tester, side view.
Figure 18a. HV presence tester, front view.
Proceed only is the installation has proven
effectively dead.
Strictly follow the information in the HV
presence tester instruction manual.
PPE (Personal Protective Equipment) adequate
for the equipment voltage class and arc flash
level shall be used.
DANGER
NOTICE
WARNING