3.5.9 Configuring robot stopping functions
Introduction
The robot stopping functions, protective and emergency stop are configured using
the
Visual SafeMove
functionality in RobotStudio.
The protective stop function can be configured to be either an
Automatic Stop
(AS)
or a
General Stop
(GS). When the protective stop function is configured as
General
Stop
(GS), the activation of the protective stop device will initiate the protective
stop in any operating mode. When the protective stop function is configured as
Automatic Stop
(AS), the activation of the protective stop device will initiate the
protective stop in automatic mode only.
Note
It is not possible to configure both
Automatic Stop
and
General Stop
on the
OmniCore V250XT without the use of a safe fieldbus.
Note
The dedicated discrete safety input to activate the protective stop function can
be configured as either
Automatic Stop
(AS) or
General Stop
(GS). For
simultaneous use of AS and GS, support for a safety protocol is required. See
option SafeMove.
For more information about safety configurations, see
Application
manual - Functional safety and SafeMove
.
Configure the robot stopping functions in Visual SafeMove
WARNING
The new settings must be verified by test before the robot is used.
Continues on next page
Product manual - OmniCore V250XT
105
3HAC073447-001 Revision: B
© Copyright 2020-2022 ABB. All rights reserved.
3 Installation and commissioning
3.5.9 Configuring robot stopping functions
Summary of Contents for OmniCore V250XT
Page 1: ...ROBOTICS Product manual OmniCore V250XT ...
Page 34: ...This page is intentionally left blank ...
Page 50: ...This page is intentionally left blank ...
Page 174: ...This page is intentionally left blank ...
Page 410: ...This page is intentionally left blank ...
Page 418: ...This page is intentionally left blank ...
Page 454: ......
Page 455: ......