7.2.5 Problem starting or connecting the FlexPendant
Description
The FlexPendant is not responding, either completely or intermittently.
No entries are possible, and no functions are available.
Note
If protective gloves are used, these must be compatible with touchscreens when
using the FlexPendant.
The FlexPendant starts but does not display the main interface.
xx1900000917
Required test equipment
Equipment needed for troubleshooting:
Note
Equipment
Multimeter
Insulating gloves
3HAC074000-008
Circuit diagram - OmniCore V250XT
, rev 04
or later
Preparations
Action
Make sure that the controller is switched on.
1
Wait 30 s - 1 min to enable start-up sequence.
Check the FlexPendant for errors and warnings.
2