Page 4–8
2101510 Rev. AG
Location
Enter information regarding meter location (24 alphanumeric digits).
Date/Time
Shows current unit Date/Time
Set Device with PCCU Date/Time
Resets device date and time to match PC
4.5.2
Stream Setup Instructions
1)
Enter the Stream ID, Location, Contract Settings and Calculation Settings (see
2)
When all
the
desired changes have been made, select
Send
and then
Next
to
move to the next screen.
3)
Complete steps 1 and 2 for each sample stream.
During the stream setup, note that each time Next is
selected, the user should see the Stream ID, located on the
first line of each screen, change value. The user must
move through all four streams even if the unit is a single
stream unit.
Table 4–2 Stream Setup Screens
Setup Tab
Available Values
Stream ID
Assign unique Identifier (10 alphanumeric digits)
Location
Enter information regarding meter location (24
alphanumeric digits).
Calibration Stream
Stream #4 (default) Stream # 1, Stream #2, Stream #3 or
Stream (Any)
Contract Settings
Value
Available Units
Contract Pressure
14.73 PSIA (default)
KPa, InH20, Mbar, InHg, PSIA, Bar, mmHg, PSFa, MPa,
Pa or kgcm2
Contract Temperature
60.00 F(default)
C, F, R or K
Relative Humidity
100.00 %(default)
Percent
Contract Hour
0 (default)
Hour (0-23)
Calculation Settings
Value
Current Calculation File
GPA-2172-1996(AGA8), ISO-6976-1995, etc.
Sum IC5 & NeoC5
No (default), Yes
C6+ Index Split Mode
Default-User Defined with C6+ Reported, 47.466% C6
35.340% C7 17.194% C8, 50% C6 50% C7 0% C8, 50%
C6 25% C7 25% C8, 57.143% C6 28.572% C7 14.285%
C8, User-Defined C6+ Not Reported.
C6, C7, C8, C9, C10`
Used to enter split percentages if desired.
4.5.3
Calibration Setup Instructions
1)
Verify that each process stream is set up to use the correct calibration
stream (Stream 4 Default).
1
File selection automatically sets the remainder of items on this screen. See PCCU Help files for more
information.
2
Note that making a selection in this field (other than User Defined) will override any values in the C6+ Split
Percent area of the Stream Setup screen.