QUICK START GUIDE
Information: Rectifier Status LEDs
Specifications and Application
Specifications and ordering information are in the Infinity S Ordering Guide available at
External Surge Protective Device (SPD) is required on all AC inputs.
Equipment and subassembly ports:
1. are suitable for connection to intra-building or unexposed wiring or cabling;
2. can be connected to shielded intra-building cabling grounded at both ends.
Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an
Integrated Ground Plane (Mesh-Bonding Network or Common Bonding Network).
Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).
Reference Documents
These documents are available at
Document
Title
CC848815341
Galaxy Pulsar Plus Product Manual
Infinity S Ordering Guide (aka product line brochure)
Safety Statements
Do not install this equipment over combustible surfaces.
Rules and Regulations - Follow all national and local rules and regulations when making field connections.
Compression Connectors
U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/Certified
field-wire conductors.
All installations - apply the appropriate connector to the correct size conductor as specified by the
connector manufacturer, using only the connector manufacturer’s recommended or approved tooling for
that connector.
Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.
Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.
Circuit Breakers and Fuses
Use only those specified in the equipment ordering guide.
Size as required by the National Electric Code (NEC) and/or local codes.
Safety Tested Limits - Refer to the equipment ratings to assure current does not exceed:
Continuous Load (List 1) - 60% of protector rating
Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.
GMT Style Fuses - Use only fuses provided with safety caps.
Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations.
Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit
breaker rating.