background image

Mounting 

This unit should be mounted on 35 mm DIN-rail, which is horizontally mounted 

inside an apparatus cabinet or similar. It is recommended that the DIN-rail is  

connected to ground. Snap on mounting, see 

Figure 6

.   

Figure  6.  Mounting NE810 with integrated DIN-clip  

18 

3BSE080633  

Summary of Contents for NE810

Page 1: ...800xA Networks NE810 User Manual ...

Page 2: ......

Page 3: ...800xA Networks NE810 User Manual ...

Page 4: ...B ABB assumes no responsibility for any errors that may appear in this document In no event shall ABB be liable for direct indirect special incidental or consequential damages of any nature or kind arising from the use of this document nor shall ABB be liable for incidental or consequential damages arising from use of any software or hard ware described in this document This document and parts the...

Page 5: ... console port 13 Powerconnection 13 I OConnection 14 LEDIndicators 16 Mounting 18 Removal 19 Cooling 19 Getting Started 20 Configuration 21 Maintenance 22 Agency Approvals and Standards Compliance 22 Notice FCC Part 15 105 22 Notice EN 55022 23 Type Tests and Environmental Conditions 23 Referring Documents 26 Cable Factory Reset on NE810 26 Proceed with Factory Reset 26 Skip the Factory Reset 27 3...

Page 6: ...ent may exceed Touch Temperature Limit according to EN IEC UL 60950 1 To reduce the risk of fire use on No 26 AWG or larger tele communication line cord Licensing Information This device contains public available software which is under the GPL license For more information see legal pdf included with all firmware releases This product in cludes software developed by the OpenSSL Project for use in ...

Page 7: ...eavy electrical interference require the use of a reliable media NE810 provides a number of solutions using fibre optic transceivers Multi or singlemode transceivers can be used to build point to point or redundant ring networks with ranges up to 120 km between each switch Our BIDI transceiver which transmits and receives data on a single fibre can be used in applications where the number of fibre...

Page 8: ... to 48 VDC Operating 19 to 60 VDC Rated Current 240 mA 24 VDC 120 mA 48 VDC Inrush current I2t 22 7 10 3 A2s 48 VDC Startup current 2 x Rated current Polarity Reverse polarity protected Redundant power input Yes Isolation to All other Connection Detachable screw terminal Connector size 0 2 2 5 mm2 AWG 24 12 Shielded cable Not required ...

Page 9: ...ge levels Logic one 12V Logic zero 1V Isolation to All other Connection Detachable screw terminal Connector size 0 2 2 5 mm2 AWG 24 12 I O Relay output Maximum voltage current 60 VDC 80 mA Contact resistance Max 30 Isolation to All other Connection Detachable screw terminal Connector size 0 2 2 5 mm2 Ω AWG 24 12 ...

Page 10: ... Mbit s manual or auto Data rate 115 2 kbit s Duplex Full or half manual or auto Data format 8 data bits no parity 1 stop bit no flow control Circuit type TNV 1 Circuit type SELV Transmission range Up to 150 m with CAT5e cable or better Connection 2 5 mm jack use only ABB cable 3BSE080212R1 Isolation to All other SFP Transceivers Connection RJ 45 auto MDI MDI X See separate data sheet Shielded cab...

Page 11: ...r TX Electrical specification IEEE std 802 3 2005 Edition Data rate 100 Mbit s or 1000 Mbit s transceivers supported Duplex Full or Auto depending on transceiver Transmission range Depending on tranceiver Connection SFP slot holding fibre transceiver or copper transceiver Number of ports 2 ...

Page 12: ...Section 3 Location of interface ports and LED s Figure 1 Location of interface ports and LED s 12 3BSE080633 ...

Page 13: ...mulator and connect with correct speed and format 115200 8N1 to the assigned port For more information about the CLI see the NEOS User Manual Power connection Figure 2 Power Connection NE810 supports redundant power connection The positive inputs are DC1 and DC2 the negative input for both supplies are COM Connect the primary voltage e g 24 VDC to the DC1 pin and return to one of the COM pins on t...

Page 14: ...onnection 14 3BSE080633 4 position Product marking Direction Description No 1 Status Output Alarm relay status contact No 2 Status Output Alarm relay status contact No 3 Digital in Input Digital in No 4 Digital in Input Digital in ...

Page 15: ...d to monitor various alarm events within the NE810 unit see NEOS User Manual An external load in series with an external voltage source is required for proper functionality The Digital in is an opto isolated digital input which can be used to monitor external events For voltage current ratings see Interface specifications Figure 4 Digital in 3BSE080633 15 ...

Page 16: ...LED Indicators Figure 5 LED Indicators 16 3BSE080633 ...

Page 17: ...rom Web or CLI DC1 OFF Unit has no power GREEN Power OK on DC1 RED Power failure on DC1 DC2 OFF Unit has no power GREEN Power OK on DC2 RED Power failure on DC2 FRNT OFF FRNT disabled GREEN FRNT OK RED FRNT Error BLINK Unit configured as FRNT Focal Point RSTP OFF RSTP disabled GREEN RSTP enabled BLINK Unit elected as RSTP STP root switch USR1 OFF Configurable see NEOS User Manual GREEN RED OFF No ...

Page 18: ...on 35 mm DIN rail which is horizontally mounted inside an apparatus cabinet or similar It is recommended that the DIN rail is connected to ground Snap on mounting see Figure 6 Figure 6 Mounting NE810 with integrated DIN clip 18 3BSE080633 ...

Page 19: ... using a screwdriver See Figure 7 Cooling Figure 7 Removing NE810 with integrated DIN clip This unit uses convection cooling To avoid obstructing the airflow around the unit use the following spacing rules Minimum spacing 25 mm 1 0 inch above below and 10 mm 0 4 inches left right the unit 3BSE080633 19 ...

Page 20: ...ement tools that can be used for configuration of the unit Web Configuration of the unit using the web browser CLI Configuration of the unit via the Command Line Interface Username admin Password CS4dmin If the computer is located in the same subnet as the switch you can easily use a web browser to configure the unit Within the web you can configure most of the available functions For advanced net...

Page 21: ...our web browser and you will be prompted with a Login screen where the default settings for Username and Pass word are Username admin Password CS4dmin Once you have logged in you can use the extensive integrated help function describing all configuration options Two common task when configuring a new switch is to assign appropriate IP settings and to change the password of the admin account The pa...

Page 22: ...h case the user will be required to correct the interference at his own expense 22 3BSE080633 Notice Corrosive environment This product has been successfully tested in a corrosion test according to IEC 60068 2 60 method 3 This means that the product meets the requirements to be placed in an environment classified as ISA S71 04 class G3 Note If the product is placed in a corrosive environment it is...

Page 23: ...e Contact 6 kV Air 8 kV Fast transients EN 61000 4 4 Power port 2 kV Signal ports 2 kV Earth port 1 kV Surge EN 61000 4 5 Power port L E 0 5 kV 12 Ohm 9 µF L L 0 5 kV 2 Ohm 18 µF L E 2 kV 42 Ohm 0 5 µF L L 2 kV 42 Ohm 0 5 µF L E 2 kV 12 Ohm 9 µF L L 1 kV 12 Ohm 9 µF Signal ports L E 1 kV 2 Ohm L E 2 kV 42Ohm 0 5 µF Power frequency magnetic field EN 61000 4 8 Enclosure 300 A m 0 16 7 50 Hz ...

Page 24: ...kHz 0 15 80 MHz Earth port 10 V 80 AM 1 kHz 0 15 80 MHz Radiated RF emission EN 55022 Enclosure Class A FCC Part 15 Class A Conducted RF emission EN 55022 Power port Class B Signal ports Class B Dielectric strength EN 60950 1 Power port to all other ports 1 5 kVrms 50 Hz 1 min Signal ports to all other ports 1 5 kVrms 50 Hz 1 min Environmental Temperatures Operating 40 to 70 C 40 to 158 F Storage ...

Page 25: ...BK 217F Operating 630 000 hours Vibration IEC 60068 2 6 sine Operating 3 13 2 Hz 1mm 13 2 100 Hz 0 7 g 5 5 30 Hz 1 5 g 30 50 Hz 0 42 mm 50 500 Hz 4 2 g Shock IEC 60068 2 27 Operating 30 g 11 ms 100 g 6 ms Bump IEC 60068 2 27 Operating 10 g 11 ms Packaging Enclosure EN 60950 1 Zinc Fire enclosure Dimension W x H x D With connectors 52 5 x 100 x 101 mm 52 5 x 119 x 101 mm Weight 0 7 kg Degree of pro...

Page 26: ...hat the ON LED is flashing red The ON LED flashing indicates that the unit is now ready to be reset to factory default You now have the choice to go ahead with the factory reset or to skip factory reset and boot as normal Proceed with Factory Reset Acknowledge that you wish to conduct the factory reset by unplugging the Ethernet cables The ON LED will stop flashing This initiates the factory reset...

Page 27: ...ctory reset process just wait for approximately 30 seconds after the ON LED starts flashing RED without unplugging the Ethernet cables The switch will conduct a normal boot with the existing settings Do not power off the unit while the factory reset process is in progress 3BSE080633 27 ...

Page 28: ...Contact us www abb com 800xA www abb com controlsystems Copyright 2017 ABB All rights reserved 3BSE080633 en B ...