![ABB NBRA-6 Series Installation And Startup Manual Download Page 52](http://html1.mh-extra.com/html/abb/nbra-6-series/nbra-6-series_installation-and-startup-manual_3350209052.webp)
Appendix B – Maximum Braking Power
B-2
Installation and Start-up Guide for NBRA-6xx
Example 2
Duration of a braking cycle is three minutes. The braking time is
40 seconds.
Result:
The maximum allowed braking power for the cycle is 37 % of
the rated value given for the reference cycle.
Example 3
Duration of a braking cycle is three minutes. The braking time is
10 seconds.
Result:
The maximum allowed braking power for the cycle is equal to
the Maximum Braking Power (
P
BRmax
) given for the reference cycle.
P
BRmax
t
P
BR
600 s
P
BR
<
P
BRmax
· 60 s
4 · 40 s
= 0.375 ·
P
BRmax
t
br
T
= Duration of the braking cycle
1.
2.
P
BR
<
P
BRmax
O.K.
T
= Duration of the braking cycle
t
br
P
BRmax
t
P
BR
600 s
P
BR
<
P
BRmax
· 60 s
4 · 10 s
= 1.5 ·
P
BRmax
1.
2.
P
BR
>
P
BRmax
Not allowed.