2.5.2  Trip time - The time is defined by the overcurrent curves (graph). I²t function is selectable. I²t curves are fixed 
and do not vary with pickup settings. If the I²t function is out, the trip times are defined as follows: Default is 
Maximum with I²t in. 
 
                           

               

                           

               

                           

               

 
 
 
 
 
2.5.3  Reset time - Real time is counted up if the current exceeds the function threshold and counted down if the 
current drops below the function threshold. Real time is set to zero when the curent drops below the power pickup 
point. 
 
2.5.4  Residual ground current - In a three phase, four wire system the ground fault functions can discriminate 
between a ground fault and a neutral current. 
 
2.5.5  Ground fault summing - The reset technique used for long-time and short-time function is applied. i.e, real time 
is counted up if the current exceeds the function threshold and counted down if the current drops below the function 
threshold. The ground function includes arcing ground summation for tripping. This feature allows arcing grounds 
occurring sufficiently close together to be summed so that their magnitude will exceed the threshold setting of the 
ground element. 
 
2.6   

Current Unbalance 

 
2.6.1  Pickup settings - 5% to 50% in increments of 1% and DISABLED. These changes can be made either via the 
keypad and LCD or the NIM communications unit. Default is DISABLED. The current unbalance function is only 
available for systems with VIM attached.  
 
 
 
2.7   

Current Sensor Thresholds 

 
 
2.7.1  Long time - 0.5X to 1.0X of sensor rating in increments of 0.1. 
 
         Short time - 2X to 10X of sensor rating in increments of 1. 
 
         Instantaneous - 3X to 12X of sensor rating in increments of 1. 
 
         Ground - 100 amps to 1200 amps 
                       300 amps to 1200 amps  
                       500 amps to 1200 amps 
                       Depending on sensor rating. See section 2.5.1 
 
 
2.8   

Information Function 

 
2.8.1  The information function consists of an LCD screen, a mechanical target, a light emitting diode (LED) and six 
keypad buttons. 
 
2.8.2  The mechanical target provides indication that the unit has caused a circuit breaker opening. Further 
information about the function such as the type of trip, LT, ST, INST, GND, I UNB, V UNB, or UV and the fault 
current is displayed when any keypad button in depressed after a trip has occurred, or can be found in the records 
menu.  

DELAY 

SETTING 

                      

100 - 800A 

SENSORS 

1600 - 2500A 

                   

3000 - 4200A 

MAX 

5.2 - 9.5 SEC 

0.59 - 1.2 SEC  0.35 - 0.50 SEC 

INT 

2.1 - 4.2 SEC 

0.24 - 0.47 SEC  0.20 - 0.32 SEC 

MIN 

0.68 - 1.3 SEC  0.07 - 0.18 SEC  0.05 - 0.17 SEC 

Courtesy of NationalSwitchgear.com

Summary of Contents for MPS-C 2000

Page 1: ...IB 6 1 2 8 1B INSTRUCTIONS FOR MPS C 2000 ELECTRONIC TRIP CONTROL UNIT ABB Courtesy of NationalSwitchgear com ...

Page 2: ...the matter should be referred to the nearest Sales Representative CONTENTS PAGE INTRODUCTION 3 FUNCTIONS 4 SETTINGS 4 RANGE SELECTION 4 LONG TIME FUNCTION 4 SHORT TIME FUNCTION 4 INSTANTANEOUS FUNCTION 5 GROUND FUNCTION 5 CURRENT UNBALANCE 6 CURRENT SENSOR THRESHOLDS 6 INFORMATION FUNCTION 6 TEST FUNCTIONS 7 VOLTAGE INTERFACE MODULE VIM 7 SETTINGS 7 MPS C 2000 SETUP INSTRUCTIONS 8 GENERAL INSTRUCT...

Page 3: ...to an accuracy of within 1 of the cicuit breaker rating The Voltage Interface Module VIM option measures voltage to an accuracy of within 1 of the circuit breaker rating and power to within 2 of the circuit breaker rating The trip unit is completely self powered taking the the tripping energy from the current through the breaker without any auxiliary power supply The complete control of the circui...

Page 4: ...des the primary amperage used as the base for the unit It is either set for the 1 X or 0 5 X the breaker rating Default is 1 X 2 2 Long Time Function 2 2 1 Threshold pickup settings The range of settings is 0 5 to 1 0 in steps of 0 1 Multipliers are used in conjunction with sensor rating and the range selector Multipliers are selected by keypad input and displayed on the LCD Default is 1 0 2 2 2 T...

Page 5: ... 9 10 11 12 DISABLED The settings are multiples of the range selector setting and are made via the keypad and the LCD screen If the short time unit is disabled the instantaneous unit cannot be disabled Default is 12 2 4 2 Trip time There is no intentional delay in the instantaneous function 2 4 3 The instantaneous unit includes a jumper on the circuit board which eliminates the possibility of inst...

Page 6: ...ground element 2 6 Current Unbalance 2 6 1 Pickup settings 5 to 50 in increments of 1 and DISABLED These changes can be made either via the keypad and LCD or the NIM communications unit Default is DISABLED The current unbalance function is only available for systems with VIM attached 2 7 Current Sensor Thresholds 2 7 1 Long time 0 5X to 1 0X of sensor rating in increments of 0 1 Short time 2X to 1...

Page 7: ...factor and frequency processing based on current data from the MPS C 2000 box c Performs calculations to determine voltage unbalance and undervoltage faults 4 2 If a VIM device is installed the MPS C 2000 unit must be connected to a NIM communications unit 4 3 If a VIM is installed in the unit a cable connects the unit to the potential transformer located on the rear of the MPS C 2000 mounting pla...

Page 8: ...setup screen Subsequent Main Menu screens are accessed by pressing the E key and the up and down keys See section 6 5 1 3 Each Main Menu has a Submenu used for entering and displaying values These are accessed by pressing the E key while in the Main Menu The up and down keys are used in the submenus to display the desired type of values or settings and the E key is pressed again to access these Th...

Page 9: ... MAIN MENU Metering Menu MAIN MENU Show Settings MAIN MENU Change Settings MAIN MENU Records Menu INITIAL SCREEN Press E or wait 3 seconds Press E Press Up and Down Arrows METER MENU Load Values Press E SETTINGS MENU MPS Settings Press E CHANGE MENU MPS Settings Press E RECORDS MENU MPS Fault Event Press E SUBMENUS See sec 6 2 See sec 6 3 See sec 6 4 See sec 6 5 This screen is displayed when unit ...

Page 10: ...ached METER MENU Demand Values Press Up and Down Arrows DEMAND VALUES Ia Press E Ib Ic In KW3p KVAr3p KWHr3p KVarHr3p These values will not be displayed if a VIM is not attached Press C Press C 6 2 METERING SUBMENU E E KEYPAD INPUT SEQUENCE FOR METERING SUBMENU E Ia Ib Ic In C E LOAD VALUES Ia DEMAND VALUES Ia METER MENU Demand Values Default screen display Press keys in this sequence to access me...

Page 11: ...SWORD Scroll up and down using arrow keys SETTINGS MENU VIM Settings Press Up and Down Arrows SHOW VIM SET V Unbal Press E V Unb Dly UV Pkup UV Delay Dmnd Intvl Press C Press C 6 3 SETTINGS SUBMENU E KEYPAD INPUT SEQUENCE FOR SETTINGS SUBMENU E Ia Ib Ic In C E SHOW SETTINGS Rating SHOW VIM SET V Unbal Default screen display Press keys in this sequence to access Settings submenus E Courtesy of Nati...

Page 12: ... In C E CHANGE SETTINGS Rating Press E PRESS E TO CHANGE SETTINGS Press C ENTER PASSWORD CHNG VIM SET V Unbal Press E Press C PRESS E TO CHANGE SETTINGS E E 6 4 1 To change settings PRESS E an asterisk will appear after the setting TOGGLE BETWEEN SETTINGS USING LEFT AND RIGHT ARROW KEYS PRESS E TO ACCEPT THEN PRESS C See instructions below for changing settings sec 6 4 1 Press keys in this sequenc...

Page 13: ...0 Volts in increments of 1 volt UNDERVOLTAGE DELAY 10 to 25 0 seconds in increments of 1 and DISABLED DEMAND INTERVAL 15 30 and 60 minutes 6 4 3 Password Protection If a password has not been programmed into the unit the PASSWORD screen can be bypassed simply by pressing E To enter a password scroll down to the PASSWORD screen in the CHANGE SETTINGS Submenu press E using the UP and DOWN keys scrol...

Page 14: ...ENU Breaker Oper BREAKER OPER Count Press E KSIa KSIb KSIc Press C Press C 6 5 RECORDS SUBMENU KEYPAD INPUT SEQUENCE FOR RECORDS SUBMENU E Ia Ib Ic In C E RECORDS MENU VIM Fault Event VIM FAULT EVENT Type Vab Vbc Vca Press E Press C E E C E Press Up and Down Arrows MPS FLT EVENT Event BREAKER OPER Count VIM FAULT EVENT Type Courtesy of NationalSwitchgear com ...

Page 15: ...IB 6 1 2 8 1B Page 15 ABB Notes Courtesy of NationalSwitchgear com ...

Page 16: ...IB 6 1 2 8 1B Page 16 ABB Notes Courtesy of NationalSwitchgear com ...

Page 17: ...IB 6 1 2 8 1B Page 17 ABB Notes Courtesy of NationalSwitchgear com ...

Page 18: ...IB 6 1 2 8 1B Page 18 ABB ABB Inc 2300 Mechanicsville Road Florence SC 29501 Phone 843 413 4700 Fax 843 413 4850 ABB Courtesy of NationalSwitchgear com ...

Reviews: