3GZF500725-144 EN 03-2023 | ABB IEC LV MOTORS

1.

Validity

This additional installation, operation, and maintenance manual is valid for water cooled mo-
tors (M3LK 250) and is to be read together with the main manual (Low Voltage Motors/Man-
ual). Additional information may be required for some machines due to special application
and/or design considerations.

Usage:

Normally, water cooled motors are manufactured to specific customer requirements. How-
ever, these instructions refer to ’standard’ water cooled motor versions.

2.

Safety Instructions

2.1.

General

General safety regulations, safety precautions and specific agreements made for each work
site shown in this document must be observed all times.

2.2.

Intended Use

Electric machines have dangerous live and rotating parts and may have hot surfaces. All oper-
ations serving transport, storage, installation, connection, commissioning, operation and
maintenance should be carried out by skilled personnel (in conformity with EN 50 110-1 / DIN
VDE 0105 / IEC 60364). Improper handling may cause serious personal injury and damage to
property.

These machines are intended for use as components for industrial and commercial installa-
tions as defined in the Machinery Directive (MD) 89/392/EEC. Commissioning is prohibited
until conformity of the end product with this directive has been established (follow particular
local safety and installation rules e.g. EN 60204).

These machines comply with the harmonized series of standards EN 60034 / DIN VDE 0530.
Their use in hazardous areas is prohibited unless they are expressly designed for such use.

Air-cooled models are typically designed for ambient temperatures of -20°C or -25°C up to
+40°C and altitudes of 1000 m above sea level, (Please refer to product specific instructions.
Ambient temperature for air-/water-cooled models should be no lower than +5°C without wa-
ter/glycol-based mixture for coolant. Do take note of deviating information on the rating
plate. Field conditions must conform to all rating plate markings. NOTE – Delete this section
once done!

2.3.

Transport storage

Report damage immediately to the transport company if damage is discovered upon delivery
and stop commissioning, if necessary. Lifting eyes are only dimensioned for the weight of the
machine, therefore do not apply extra loads. Ensure the use of correct lifting eyes and if
needed, use suitable lifting equipment (e.g.rope guides). Remove shipping braces (e.g. bear-
ing locks, vibration dampers) before commissioning and store these for further use.

When storing machines make sure that the location is dry, and free from dust and vibration
to avoid bearing damage. Measure insulation resistance before commissioning. Limit values

Summary of Contents for M3LK 250

Page 1: ... ADDITIONAL MOTOR MANUAL Low voltage Water cooled motors motor type M3LK 250 ...

Page 2: ...2 3GZF500725 144 EN 03 2023 ABB IEC LV MOTORS ...

Page 3: ...Transport storage 4 2 4 Installation 5 3 Electrical connection 5 4 Operation 6 5 Maintenance and servicing 7 6 Handling 7 7 Lifting 8 8 Water cooling 9 9 Connection 9 9 1 Requirements for cooling water 9 9 2 Filling or draining cooling water 10 10 Consendation drain holes 10 11 Water leakage detector 10 12 Figures 11 Contactus 13 ...

Page 4: ...g is prohibited until conformity of the end product with this directive has been established follow particular local safety and installation rules e g EN 60204 These machines comply with the harmonized series of standards EN 60034 DIN VDE 0530 Their use in hazardous areas is prohibited unless they are expressly designed for such use Air cooled models are typically designed for ambient temperatures...

Page 5: ...of the shaft end key establish mechanical bal ance Make the necessary ventilation and cooling system connections making sure that the ventila tion does not get obstructed and that exhaust air either from the current machine or other machines is not drawn into the ventilation intake The terminals of a machine with frequency converter supply may be energized even when the machine is at a standstill ...

Page 6: ...s and the box itself in a dust and watertight manner Lock the key when the ma chine is run without coupling For machines with accessories check that they function before commissioning The proper installation e g segregation of signal and power lines screened cables etc lies within the installer s responsibility 4 Operation Do not exceed the maximum allowed speed of the machine See product specific...

Page 7: ...us machines must only be serviced by repair shops qualified and authorized by ABB For more information concerning service of permanent magnet syn chronous machines please contact ABB Follow manufacturer s operating instructions For further details see product specific manu als or contact ABB Motor has special encoder and bearings system which requires a special care during a maintenance Separate s...

Page 8: ...ebolts provided with the motor must be used for lifting the motor They must not be used to lift the motor when it is attached to other equipment Lifting lugs for auxiliaries e g brakes or terminal boxes must not be used for lifting the mo tor Because of different output mounting arrangements and auxiliary equipment motors with the same frame may have a different center of gravity Damaged lifting l...

Page 9: ...cording to the standard EN 10025 S235_ or S355 This material is prone to corrosion in saline and foul water The corrosion products and fouling deposits might block the water flow in the ducts That s why it is important to use pure water in the cooling system Standard values for the cooling water to be used in the cooling system pH 6 5 9 5 Alkalinity CaCO3 1 mmol l Chloride Cl 120 mg l Conductivity...

Page 10: ...low into the motor until it comes out of the air gap Close the air gap with a plug and seal the joint with sealing tape or strip Filling must be done carefully so that no air is left in the motor s cooling channels Check for possible leaks after the piping and joints have been con nected Emptying can be done with pressurized air After emptying the plugs must be re fitted and the seals of the joint...

Page 11: ...ed accord ing to the mounting arrangement of the motor The maximum deviation from the vertical axis line is 30 Electrical connection of float switch 12 Figures Figure 1 Condensation drain hole locations Open and close position of plugs max voltage max current 1 A switch capacity 230 V DC AC 100 VA Drain hole plugs condensation ...

Page 12: ...GN1 SVK27A _NO closed contact at alarm Figure 3 Sectional view of water leakage detector and typical connection diagram of float switch Bleeding plug water cooling system Water leakage detector water cooling system Water outlet EN10556 Rp 1 water cooling system Water inlet EN10556 Rp 1 water cooling system ...

Page 13: ... Contact us abb com motors generators Copyright 2023 ABB All rights reserved Specifications subject to change without notice 3GZF500725 144 EN 03 2023 ...

Reviews: