M1M FIRMWARE UPDATE

 

 

 

4/8

 

• Baud Rate = 19200

 

• Protocol = 8E1 (8 bit data, even parity and 1 bit stop)

 

• RTU address for Master Device = 1

 

• RTU address for M1M slave device: to be inserted starting from 2 to 247.

 

TIP

: Each device shall be provided with a different slave address. 

Otherwise, only one of the devices with the same slave address 

can be recognized.

 

2.2

 

M1M Ethernet 

 

(M1M 20 Ethernet, M1M 30 Ethernet)

 

A.

 

Steps to set Modbus TCP/IP communication parameters are described in 

section "Communication (COMM)" of M1M 20 and M1M 30 user manual.

 

On the device, go to "MENU"

"CONF"

"COMM" 

 

In the "DHCP" section, select between YES and NO.

 

In the "IP" section, select the desired address of the device (in “Static 

Configuration”) or read the current IP address if the DHCP support is ena-

bled. The default IP address is: 192.168.2.252.

 

TIP

: In case of ABB cloud access point, DHCP on M1M should be 

disabled (as default) and its TCP port, which is already enabled, 

should be at the default value (502).

 

TIP

: In case of ABB cloud access point, IP of M1M shall be in the 

range of the sub-network where the cloud access point is con-

nected, which must be provided with access to the internet.

 

B.

 

According to the architecture, follow the instructions

 

1.

 

M1M directly connected to laptop via Ethernet port

 

Laptop shall be connected to same Ethernet network where the 

M1M is connected. To access IP settings in Windows, access laptop 

“Control Panel” 

 ”Network and Sharing Center” 

 ”Change 

adapter settings” 

 right click on “Local Area Connection (LAN)” 

 ”Properties”>”Internet Protocol Version” and “Properties”.

 

2.

 

M1M connected in the local area network 

 

Laptop shall be connected to the same local area network as M1M.

 

 

Summary of Contents for M1M

Page 1: ...9AKK108466A3466 1 8 COMMISSIONING GUIDELINE M1M Firmware update Getting started ...

Page 2: ...Modbus RTU M4M 15 Modbus M1M 20 Modbus M1M 20 I O M1M 30 Modbus M1M 30 I O 3 2 2 M1M Ethernet M1M 20 Ethernet M1M 30 Ethernet 4 3 Procedure via M1M FW update tool 5 3 1 Connection via Modbus RTU M1M Modbus 5 3 2 Connection via Modbus TCP IP M1M Ethernet 6 3 3 System update Error Bookmark not defined 3 4 FW update 7 ...

Page 3: ...onnected to the ABB power meter is cor rectly connected TIP in case the device is not communicating re cable the device by switching terminals B Steps to set Modbus RTU communication parameters are described in section Communication COMM of M1M 15 M1M 20 and M1M 30 user manuals On the device go to MENU CONF COMM In the ADDR section select an address from 1 to 247 In the BAUD section select the des...

Page 4: ...ss if the DHCP support is ena bled The default IP address is 192 168 2 252 TIP In case of ABB cloud access point DHCP on M1M should be disabled as default and its TCP port which is already enabled should be at the default value 502 TIP In case of ABB cloud access point IP of M1M shall be in the range of the sub network where the cloud access point is con nected which must be provided with access t...

Page 5: ...meters of the device Address enter the value of the device that can be found in the MENU CONF COMM ADDR page of M1M options from 1 to 247 Port select the port that is being used to connect the device to the computer COM3 for RS 232 port COM4 for USB port Baudrate enter the value of the device that can be found in the MENU CONF COMM BAUD page of M1M options 9600 19200 38400 57600 115200 Byte enter ...

Page 6: ...hernet MB It is needed to enter the main communication parameters of the device IP Address enter the value of the device that can be found in the MENU CONF COMM IP page of M1M default 192 168 2 252 Port select the port that is being used to connect the device to the computer default 502 ...

Page 7: ...TE 7 8 3 2 FW update A Download the M1M FW version from the ABB Library here B Please click on Open File C Select the latest M1M FW version available enc file previously extracted from the zip D Please click on Download ...

Page 8: ...ting with the M1M during the FW update process in or der to have a successful update E Please do not unplug the M1M s auxiliary power supply during this opera tion F As the FW update is completed successfully you can check the installed FW version on your M1M directly on the MENU CONF UNIT INFO page ...

Reviews: