ABB LST300 Series Description With Wiring Suggestions Download Page 3

Analog output

The LST300 has a 4-20 mA analog output for

transmitting measurements and alarms.

-

20 mA output and power input are

transmitted on the same wire.

-

The output current is a process variable

under normal conditions. It can also be

used as fault protection or as a fixed

value to indicate the alarm situation.

-

 

 Low alarm value can be configured in the

range of 3.5 mA - 3.6 mA.

-

 

The high alarm value can be configured in

the range of 21 mA - 22.6 mA.

-

 

The refresh frequency of  4 - 20 mA output is

0.2 seconds.

HART Communication

HART protocol is used for digital communication

between process control system/PC, handheld

terminal equipment and LST300. It can be used to

send all equipment and measurement point

parameters from transmitter to process control

system or PC.

It also provides a way to reconfigure the

transmitter. Digital communication utilizes

alternating current (4 - 20 mA) superimposed on

analog output, without affecting any instrument

connected to the output.

-

HART communication and power are

transmitted on the same cable. No

additional cables are required.

-

HART communication requires an

additional resistor.

-

The minimum resistance of the resistor is

250 ohms. Resistors on power lines can

cause voltage drop, which should be

considered to ensure that the supply

voltage for LST300 is higher than the

minimum rated input voltage.

-

The baud rate of HART communication is

1200.

Ground Connection

The LST300 needs to be grounded at the terminals,

as shown in Fig. 2.

-

LST300 has two ground connectors (PE).

Effective grounding connection is needed

to achieve optimal EMC protection.

-

If LST300 is used in hazardous

environments (Zone 1 and Zone 1 and Zone

2), all grounding must comply with

explosion-proof requirements.

Terminal connection example

Fig. 3 Electrical Connection - HART Version

1. Power Supply

2. Remote Display

3. Handheld Terminal Equipment

4. External grounding connection

5. Internal grounding connection

6. Cable entrance

Explosion-proof transmitters

must be repaired by the

manufacturer or approved by

qualified technical experts after

repair. Please observe the

relevant safety precautions

before, during and after the

repair work.

Warning