PROFIBUS DP® Communication
PNO ID no.
0×9655 Actuators with DP/V0 communication (cyclic data traffic)
0×09EC Actuators with DP/V1 communication (cyclic and acyclic data traffic)
Communication protocol
PROFIBUS PA® Profile V3.0 Class B in accordance with IEC 50170 / EN 50170 (DIN 19245)
Bus cable
Twisted, shielded copper wire acc. to IEC 50170 / EN 50170
Interface
EIA-485 (RS485) acc. to IEC 50170 / EN 50170
Permissible baud rates
93.75 Kbit/s
187.5 Kbit/s
500 Kbit/s
1500 Kbit/s
Automatic baud rate detection
Bus address
0 to 126, default address 126
Set Slave Address service is supported
Bus termination
Connectable active bus termination. Power supply from electronic unit
Block types
1 analog input function block
1 transducer block
1 physical block
Failsafe
Failsafe function is supported.
Configurable function for downtime of bus communication
• Lock in last position
• Drive to safety position
• Adjust with last effective set point
Adjustable time delay
Modules for cyclic communication
8 standards-compliant modules and 3 manufacturer-specific modules are available.*
SP (Short)
SP (Long)
RCAS_OUT
SP+RPOS_D
SP+CHECKBACK
SP+RPOS_D+CHECKBACK
RCHECKBACK
SP+RRPOS_D+CHECKBACK
STANDARD
SP+RB+MESSEING
SP+RB+ENL_DIAG
Acyclic communication
Full parameterization and configurability via Master Class 2 and DTM
Default settings
PROFIBUS DP® communication
on page 11
Digital outputs 1 and 2
In addition to the PROFIBUS®-communication, there are 2 digital outputs.
Potential-free relay contact, max. 60 V, 150 mA
Default setting:
Digital output 1 End position signal 0 %
Digital output 2 End position signal 100 %
Individual settings
See data sheet ‘DS/CONTRAC/SETTING’ or available upon request.