Test Results
Section 4 Linking Device Diagnostics
76
3BDD011677-600 A
The extended RAM tests will be performed once during the next system restart. Due
to the runtime needed to carry out these tests, the system booting time is prolonged.
Test Results
If any errors are found during the tests, this will be indicated by a red F-LED (F =
Failure) on the front side of the linking device hardware. A flashing of the F-LED
indicates that an error has occurred but that the system can still be booted. In this
case, the test result can be queried on the web pages of the linking device via the
Hardware Diagnostics link.
A severe hardware defect can make system booting impossible. This state is
indicated by steady light of the F-LED while the R-LED is off.
Built-in Web Server
General information about the linking device can be queried via the web pages of
the built-in web server, refer to
requires a standard web browser supporting JavaScript (e. g. Microsoft Internet
Explorer) on a PC that is connected to the linking device via Ethernet, refer to
Setting Up an IP Connection between PC and Linking Device
configuring an Ethernet connection between a PC and the linking device.
For details on status indication refer to
From System 800xA 6.0 onwards, the LD 800HSE web server Disable
functionality is performed only after LD initialization and download of first
configuration parameters. The LD 800HSE web server page can be opened only
if it is enabled in Fieldbus Builder FF and is automatically disabled after one
hour.
The web server page is displayed based on the type of user (Operat/Config/Diag)
logged in.
Summary of Contents for LD 800HSE
Page 2: ......
Page 3: ...Device Management FOUNDATION Fieldbus Linking Device LD 800HSE and LD 800HSE EX V3 6 0 0 ...
Page 102: ...Device Redundancy Appendix B Limits and Performance Data 102 3BDD011677 600 A ...
Page 124: ...Redundancy Behavior Appendix C Technical Reference 124 3BDD011677 600 A ...
Page 135: ......