background image

41-923.4M

8

With the moving contact in the normally closed posi-
tion, i.e., against the right side of the bridge, screw in
the stationary contact until both contacts just close.
Then screw in the stationary contact approximately
one-quarter turn farther to provide the correct
amount of follow for KR & TC type carrier, one-half
turn for TA-3 tones.

The clamp holding the stationary contact housing
need not be loosened for the adjustment since the
clamp utilizes a spring-type action in holding the sta-
tionary contact in position.

The sensitivity adjustment is made by varying the
tension of the spiral spring attached to the moving
element assembly. The spring is adjusted by placing
a screwdriver or similar tool into one of the notches
located on the periphery of the spring adjuster and
rotating it. The spring adjuster is located on the
underside of the bridge and is held in place by a
spring type clamp that does not have to be loosened
prior to making the necessary adjustments.

Pass 0.5 amp of ac through relay terminals 16 and
17. Adjust the spring until the contact just opens. In a
similar manner the pick-up value can be adjusted for
any value between .5 and 1.0 amp.

7.1.2.

Auxiliary Units (CSP and CSG)

The two contactor switches, CSP and CSG, have
adjustable plunger travel. Adjust the stationary core
and the moving core of 1/64” when the switch is
picked up. This can be done by turning the relay
upside-down and screwing up the core screw of the
switch until the contacts just separate. Then back off
the core screw approximately one turn and lock in
place. This prevents the moving core from striking
and sticking to the stationary core because of resid-
ual magnetism. Adjust the contact clearance for
approximately 1/32” by means of the two small nuts
on either side of the Micarta disc.

Each contactor switch has a section of a tapped
resistor in series with it, and will pick up positively
when rated trip circuit voltages is applied across the
coil and its section of the resistor.

The units should operate at 24 volts for the 48-volt
relay, 60 volts for the 125-volt relay and 120 volts for

250-volt relay. These units have an intermittent rat-
ing, and should not be energized for more than a few
seconds.

7.1.3.

Squelch Unit

Check operation with timer. Adjust series resistor to
measure approximately 5000 ohms for 125 Vdc
relays and for 13000 ohms for 250 Vdc relay. With
armature closed, adjust the residual air gap to be
.002” – .003”. Contact gap should measure from
.020” to .035”. Check for dropout time between .140
and .160 seconds. If necessary dropout time can be
adjusted by changing the residual air gap. After final
adjustment the gap should be at lease .002”. The
pickup time should be below 16 milliseconds at -20%
rated dc voltage. If necessary readjust series resis-
tor.

7.1.4.

Operation Indicator

The operation indicator should pickup and drop the
indicator target when the current is between 1 and
1.2 amperes dc.

Make sure that the target drops freely when the unit
operates.

7.2.

ZENER DIODE TEST

7.2.1.

Forward Characteristics

Pass 200 mA of dc current through terminals 8 and 9
with positive on terminal 8. Measure voltage drop
across terminals 8 and 9 with positive on 9. The volt-
age drop should not exceed 3.5 volts.

7.2.2.

Reverse Characteristics – 
Breakdown Voltage

The breakdown Voltage is determined by increasing
voltage across terminals 8 and 9 with positive on 9.
Place 10,000 ohm resistor in series with ammeter.
Increase voltage until current reads .25 mA. Measure
dc voltage across terminals 8 and 9. The voltage
should be between 160 and 240 volts for 48 and 125
Vdc rated relays; and 320 to 480 volts for 250 Vdc
rated relays. 

DO NOT

 exceed 3.0 mA current in the

circuit.

Summary of Contents for KA-4

Page 1: ......

Page 2: ...41 923 4M 2 Figure 1 Type KA 4 Relay without case Front View ...

Page 3: ...ternal Schematic of the Type KA 4 Relay for TC Carrier Set Figure 4 Internal Schematic of the Type KA 4 Relay with Modified Carrier Stop to Terminal 11 for TC Carrier Set Figure 5 Internal Schematic of the Type KA 4 Relay for the TA 3 tones Sub 1 3491A17 Sub 1 349A16 Sub 3 629A389 Sub 9 629A476 ...

Page 4: ... operation of the sec ond zone or KD 10 distance relay and the CSG switch by the operation of the directional and over current units of the KRD 4 ground relay The contacts of the two switches are connected in parallel as shown in the internal schematic The operation of either of these switches connects the carrier control circuit to negative to stop carrier and energizes the RRT operating coil of ...

Page 5: ...e type unit of slow release type In these relays an electromagnet attracts a right angle iron bracket which in turn operates one nor mally open contact The slow release is obtained by a copper slug located at the end opposite from the armature When the coil becomes deenergized the change in flux through the slug results in an electro motive force and associated current in it This current produces ...

Page 6: ...in 475 and 525 amp 6 1 2 Auxiliary Units CSP and CGS Each contactor switch has a section of a tapped resistor in series with it and will pick up positively when rated control voltage is applied across the coil and its section of the resistor These units should operate at 24 volts for the 48 volt relay 60 volts for the 125 volt relay and 120 volts for 250 volt relay These units have an intermittent...

Page 7: ...tal and CSP is located on the right hand pedestal on the relay front view Apply rated voltage across the RRT coil and the RRT coil resistor observing polarity as shown in the internal schematic The armature should move to the left To the holding coil RRH relay terminals apply direct current observing correct polarity Increase the cur rent until the armature moves to the right The arma ture should ...

Page 8: ...the two small nuts on either side of the Micarta disc Each contactor switch has a section of a tapped resistor in series with it and will pick up positively when rated trip circuit voltages is applied across the coil and its section of the resistor The units should operate at 24 volts for the 48 volt relay 60 volts for the 125 volt relay and 120 volts for 250 volt relay These units have an intermi...

Page 9: ...oint Increase the holding coil current to 60 milliamperes and adjust the left hand shunt screw until the arma ture resets or moves to the right If the armature resets at a value of current less than 60 milliam peres the left hand shunt screw should be turned out This will increase the reset value of the armature and provide for the correct 60 milliampere reset value Minor adjustments of both shunt...

Page 10: ...eck pick up at 8 mA 5 instead of 80 mA Dropout should be between 4 and 6 mA instead of 40 and 60 mA 8 0 RENEWAL PARTS Repair work can be done most satisfactorily at the factory However interchangeable parts can be fur nished to the customers who are equipped for doing repair work When ordering parts always give the complete nameplate data 9 0 ENERGY REQUIREMENTS 9 1 CURRENT BURDEN AT 60 CYCLES 9 2...

Page 11: ...41 923 4M 11 THIS PAGE LEFT BLANK ...

Page 12: ...41 923 4M 12 Figure 8 Typical External Schematic of a KA 4 Relay in a KD 4 TC Blocking System Sub 4 5307D96 ...

Page 13: ...41 923 4M 13 Figure 8 Typical External Schematic of a KA 4 Relay in a KD 4 TC Blocking System Sub 4 5307D96 ...

Page 14: ...41 923 4M 14 Figure 9A Typical External Schematic of a KA 4 Relay in a KD 10 TC Blocking System ...

Page 15: ...41 923 4M 15 Figure 9B Typical External Schematic of a KA 4 Relay in a KD 10 TC Blocking System ...

Page 16: ......

Reviews: